4. Fuses and breakers:
Properly sized fuses and breakers should be installed between each important junctions, i.e. PV <->
Controller, Controller <-> Battery, Battery <-> Inverter, and Inverter <-> AC loads. As a general rule of
thumb, follow the formula below when selecting a properly sized fuse/breaker:
Amp = 1.25 * Isc of c
Amp = 1.25 * Isc of cAmp = 1.25 * Isc of c
Amp = 1.25 * Isc of circuit current
ircuit currentircuit current
ircuit current
For more information, please consult your electrician for guidance.
5. Communication and Remote Monitoring:
Remote monitoring can be achieved by connecting the detached LCD module to the remote control
port with ONLY straight
straightstraight
straight-
--
-through 1
through 1through 1
through 1-
--
-to
toto
to-
--
-1
11
1
RJ45 cable
RJ45 cableRJ45 cable
RJ45 cable.
*
DO NOT use cross-over or any other type RJ45 cable as this can cause monitor to function
incorrectly or cause damage!
6. Battery:
Connect the battery terminals to the battery terminals on PIP-LC and make sure polarity is correct!
WARNING:
WARNING: WARNING:
WARNING: incorrect polarity may blow fuse and cause internal damage to inverter.
incorrect polarity may blow fuse and cause internal damage to inverter.incorrect polarity may blow fuse and cause internal damage to inverter.
incorrect polarity may blow fuse and cause internal damage to inverter.
Recommended battery wire size:
Model Max Current Wire Size
800W 67amp AWG 4
1.6KW 67amp AWG 4
2.4KW 100amp AWG 2
4.0KW 167amp AWG 00
6.0KW 125amp AWG 0
8.0KW 167amp AWG 00
NOTE:
for 6KW/8KW inverters, battery resistor cable
battery resistor cablebattery resistor cable
battery resistor cable (see below) may be included for your
convenience. Be sure to apply it in between the battery and inverter for at least 5 seconds before
directly connecting the battery to your inverter terminal. This will help reduce the sparks during