Inspection
InspectionInspection
Inspection
1. The system may be installed and wired only by qualified electricians in accordance with applicable
safety regulations.
2. When installing the electrical wiring, please note the nominal amperage of your incoming feeder.
3. Inspect the packaging carton and its content for damage. Please inform your shipper immediately
should you find signs of damage. Please keep original packaging in a safe space for future use.
4. Please ensure that incoming feeder is isolated and secured to prevent it from being switched back
again.
B
BB
B-
--
-3
33
3-
--
-2 Connect
2 Connect2 Connect
2 Connection
ionion
ion
1. Grounding
-AC and DC Grounding: The PIP-LC has to be connected to a grounded permanent wiring system; and
the array has to be grounded as well. AC and DC are separately grounded.
2. AC Input / Output Terminals
-Utility (Input):
Recommended AC wire size:
Capacity \ Input voltage
100/110/120V 220/230/240V
800W AWG 12 / 3.5mm
2
AWG 12 / 3.5mm
2
1.6KW AWG 12 / 3.5mm
2
AWG 12 / 3.5mm
2
2.4KW AWG 10 / 5.5mm
2
AWG 12 / 3.5mm
2
4.0KW AWG 6 / 14 mm
2
AWG 10 / 5.5mm
2
6.0KW AWG 4 / 22 mm
2
AWG 8 / 8.0 mm
2
8.0KW N/A AWG 6 / 14 mm
2
11.0KW N/A AWG 4 / 22 mm
2
-Load (Output):
Recommended AC wire size:
Capacity \ Input voltage
100/110/120V 220/230/240V
800W AWG 12 / 3.5mm
2
AWG 12 / 3.5mm
2
1.6KW AWG 12 / 3.5mm
2
AWG 12 / 3.5mm
2
2.4KW AWG 10 / 5.5mm
2
AWG 12 / 3.5mm
2
4.0KW AWG 6 / 14 mm
2
AWG 10 / 5.5mm
2
6.0KW AWG 4 / 22 mm
2
AWG 8 / 8.0 mm
2
8.0KW N/A AWG 6 / 14 mm
2
11.0KW N/A AWG 4 / 22 mm
2
NOTE: each recommended wire size above applies to EACH
EACHEACH
EACH of L/N/G inside a power cable.