User manual

32
Appendix: Approximate Back-up Time Table
Model Load (VA) Backup Time @24Vdc 100Ah (min) Backup Time @24Vdc 200Ah (min)
1KVA
200 766 1610
400 335 766
600 198 503
800 139 339
1000 112 269
2KVA
200 766 1610
400 335 766
600 198 503
800 139 339
1000 112 269
1200 95 227
1400 81 176
1600 62 140
1800 55 125
2000 50 112
3KVA
300 449 1100
600 222 525
900 124 303
1200 95 227
1500 68 164
1800 56 126
2100 48 108
2400 35 94
2700 31 74
3000 28 67
Model Load (VA) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
1KVA
100 2529 5058
200 1264 2529
300 843 1686
400 608 1279
500 482 1035
600 406 872
700 310 710
800 268 615
900 231 540
1000 186 471