User Manual
- 8 -
A. Through the serial console port with the following settings:
Baudrate=115200 bps, Parity=None, Data bits=8, Stop bits =1,
Flow Control=None
ATTENTION
Remember to choose the
“VT100” terminal type. Use the console
cable to connect a PC to the UC-8100A-ME-T's serial console port
B. Using SSH over the network. Refer to the following IP addresses and
login information:
Default IP Address
Netmask
LAN 1
192.168.3.127
255.255.255.0
LAN 2
192.168.4.127
255.255.255.0
Login: moxa
Password: moxa
ATTENTION
•
The
equipment shall only be used in an area of not more than
pollution degree 2, as defined in IEC/EN 60664-1.
•
The equipment shall be installed in an enclosure that
provides a degree of protection not less than IP 54 in
accordance with IEC/EN 60079-15 and acce
ssible only by the
use of a tool.
•
These devices are open-
type devices that are to be installed
in an enclosure with tool removable cover or door, suitable
for the environment.
•
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, and D or non-hazardous locations only.
•
ANTENNAS INTENDED FOR USE IN CLASS I, DIVISION 2
HAZARDOUS LOCATIONS MUST BE INSTALLED WITHIN THE
END-USE ENCLOSURE. FOR REMOTE MOUNTING IN AN
UNCLASSIFIED LOCATION, ROUTING AND INSTALLATION OF
THE ANTENNAS SHALL BE IN ACC
ORDANCE WITH NATIONAL
ELECTRICAL CODE REQUIREMENTS (NEC/CEC) Sec.
501.10(b).
•
The “USB, RS-232/422/485 serial ports, LAN1, LAN2, and
Console ports” and Reset Button may only be accessed for
equipment set-up, installation, and maintenance at a
non-hazardous location. These ports and their associated
interconnecting cables must remain inaccessible within the
hazardous location.