User Manual
- 7 - 
4.  Standards Covered:  
EN 60079-0:2012+A11:2013, IEC 60079-0 Ed 6.0,   
EN 60079-15:2010, IEC 60079-15 Ed 4.0 
5.  The conditions of safe usage: 
•  The Ethernet Communications Devices are intended for 
mounting in a tool-accessible ATEX-Certified or IECEx-Certified 
(for models with the suffix -CT or -IEX) IP54 enclosure and 
used in an area of not more than pollution degree 2 as defined 
by IEC/EN 60664-1 or IEC 60664-1 (for models with the suffix -
CT or -IEX). 
•  Conductors suitable for use in an ambient temperature greater 
than 91°C must be used for the power supply terminal. 
•  A 4 mm
2
 conductor must be used when connection to the 
external grounding screw is utilized. 
•  Provisions shall be made, either in the equipment or external to 
the equipment, to prevent the peak rated voltage being 
exceeded by the transient disturbances of more than 140%. 
6.  Terminal block information. 
•  Input Terminal Block (J1)—Dinkle Enterprise Co, Ltd, Cat. No. 
5EHDR-08P, rated 300V, 10A, 105℃, suitable for 28-12 AWG 
(0.12-3.31 mm²) wire size, torque value 4.5 lb-in (0.508 N-m). 
Terminal blocks do not accommodate more than one individual 
conductor per clamping point. Mechanically secured by two 
screws. 
•  Signal Channel Terminal Block (J2, for the NPort IA5150A 
Series only)—Dinkle Enterprise Co, Ltd, Cat. No. 5EHDR-05P, 
rated 300V, 10A, 105℃, mating with Cat. No. 5ESDV-05P, 
rated 300V, 10A, 105℃, suitable for 28-12 AWG (0.12-
3.31mm²) wire size, torque value 4.5 lb-in (0.508 N-m). 
Terminal blocks do not accommodate more than one individual 
conductor per clamping point. Mechanically secured by two 
screws. 
7.  Address: Moxa Inc, 4th Fl, No.135, Lane 235, Baoqiao Road, 
Xindian District, New Taipei City, 231 Taiwan 
Pull-high, Pull-low, and Terminator for RS-485 
Remove the NPort IA5000A’s top cover and you will find DIP switches 
to adjust each serial port’s pull-high, pull-low, and terminator. 
NPort IA5150A Series 
NPort IA5250A Series 