User Manual
- 6 - 
To add a 120 Ω termination resistor, set switch 3 on the port’s 
assigned DIP switch to ON; set switch 3 to OFF (the default setting) to 
disable the termination resistor. 
To set the pull-up/down resistors to 150 KΩ, set switches 1 and 2 on 
the port’s assigned DIP switch to OFF. This is the default setting. 
To set the pull-up/down resistors to 1 KΩ, set switches 1 and 2 on 
the port’s assigned DIP switch to ON. 
Pull-Up/Down Resistors for the RS-485 Port 
SW1 (Serial 1) 
SW2 (Serial 2) 
DIP 1 
Pull-up resistor 
DIP 2 
Pull-down 
resistor 
DIP 3 
Terminal resistor 
ON 
1 KΩ 
1 KΩ 
120 Ω 
OFF (Default) 
150 KΩ 
150 KΩ 
N/A 
NOTE 
Do not use the 1 KΩ setting while in RS-232 mode. Doing so will 
degrade the RS
-232 signals and reduce the effective 
communication distance. 
Software Installation Information 
For software installation, download the relative utilities from Moxa’s 
website: 
https://www.moxa.com/support/support_home.aspx?isSearchShow=1
•  Download the NPort Windows Driver Manager and install it as 
the driver to run with Real COM mode of the NPort Series. 
•  Execute NPort Windows Driver Manager; then map the virtual 
COM ports on your Windows platform. 
•  You may refer to the DB9 Male pin assignment section to loop 
back pin 2 and pin 3 for the RS-232 interface to carry out a 
self-test on the device. 
•  Use HyperTerminal or a similar program (you may download 
Moxa’s program, called PComm Lite) to test whether the device 
is good or not. 
Setting the IP Address 
The factory default IP settings are assigned as follows: 
NPort IA5000A-I/O Series 
LAN 
IP 
Netmask 
Static 
192.168.127.254 
255.255.255.0 
NPort IAW5000A-I/O Series 
LAN 
IP 
Netmask 
Static 
192.168.126.254 
255.255.255.0 