User Manual

- 6 -
To add a 120 Ω termination resistor, set switch 3 on the ports
assigned DIP switch to ON; set switch 3 to OFF (the default setting) to
disable the termination resistor.
To set the pull-up/down resistors to 150 KΩ, set switches 1 and 2 on
the ports assigned DIP switch to OFF. This is the default setting.
To set the pull-up/down resistors to 1 KΩ, set switches 1 and 2 on
the ports assigned DIP switch to ON.
Pull-Up/Down Resistors for the RS-485 Port
SW1 (Serial 1)
SW2 (Serial 2)
DIP 1
Pull-up resistor
DIP 2
Pull-down
resistor
DIP 3
Terminal resistor
ON
1 KΩ
1 KΩ
120 Ω
OFF (Default)
150 KΩ
150 KΩ
N/A
NOTE
Do not use the 1 KΩ setting while in RS-232 mode. Doing so will
degrade the RS
-232 signals and reduce the effective
communication distance.
Software Installation Information
For software installation, download the relative utilities from Moxa’s
website:
https://www.moxa.com/support/support_home.aspx?isSearchShow=1
Download the NPort Windows Driver Manager and install it as
the driver to run with Real COM mode of the NPort Series.
Execute NPort Windows Driver Manager; then map the virtual
COM ports on your Windows platform.
You may refer to the DB9 Male pin assignment section to loop
back pin 2 and pin 3 for the RS-232 interface to carry out a
self-test on the device.
Use HyperTerminal or a similar program (you may download
Moxa’s program, called PComm Lite) to test whether the device
is good or not.
Setting the IP Address
The factory default IP settings are assigned as follows:
NPort IA5000A-I/O Series
LAN
IP
Netmask
Static
192.168.127.254
255.255.255.0
NPort IAW5000A-I/O Series
LAN
IP
Netmask
Static
192.168.126.254
255.255.255.0