Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Over-Voltage Protection 45 VDC
Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector) 2
Auto MDI/MDI-X connection
Magnetic Isolation Protection 1.5 kV (built-in)
Ethernet Software Features
Industrial Protocols MQTT, MTConnect
Configuration Options Web Console (HTTP/HTTPS), Windows Utility, Telnet Console, Serial Console
Management DHCP Client, DNS, HTTP, IPv4, SMTP, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, ICMP
Windows Real COM Drivers Windows 95/98/ME/NT/2000, Windows XP/2003/Vista/2008/7/8/8.1/10 (x86/x64),
Windows 2008 R2/2012/2012 R2/2016/2019 (x64), Windows Embedded CE 5.0/6.0,
Windows XP Embedded
Linux Real TTY Drivers Kernel versions: 2.4.x, 2.6.x, 3.x, 4.x, and 5.x
Fixed TTY Drivers SCO UNIX, SCO OpenServer, UnixWare 7, QNX 4.25, QNX 6, Solaris 10, FreeBSD, AIX 5.
x, HP-UX 11i, Mac OS X
Android API Android 3.1.x and later
MIB MIB-II
Serial Interface
Connector DB9 male
No. of Ports NPort IA5150A models: 1
NPort IA5250A models: 2
Serial Standards RS-232, RS-422, RS-485
Baudrate 50 bps to 921.6 kbps
Data Bits 5, 6, 7, 8
Stop Bits 1, 1.5, 2
Parity None, Even, Odd, Space, Mark
Flow Control None, RTS/CTS, XON/XOFF
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485 120 ohms
Surge 4 kV
Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND