Datasheet

8
www.moxa.com
info@moxa.com
Remote I/O
M-3802
Status
System Bus
M-3810
Status
System Bus
Analog Input Modules
8-channel analog input modules, 12-bit resolution
M-3802
Status
System Bus
M-3802: 8 analog inputs, 4 to 20 mA, 12 bits
Resolution in Ranges: 12 bits, 3.91 µA/bit
Input Current Range: 4 to 20 mA (single-ended)
Data Format: 16-bit integer (2’s complement)
Accuracy:
• ±0.1%, FSR @ 25°C
• ±0.3%, FSR @ 0°C, 60°C
Input Impedance: 120 ohms
Conversion Time: 4 ms for all channels
Power Consumption: Max. 150 mA @ 5 VDC
Isolation: I/O to logic (photocoupler isolation)
Wiring: I/O cable max. AWG14
M-3810: 8 analog inputs, 0 to 10 V, 12 bits
Resolution in Ranges: 12 bits, 2.44 mV/bit
Input Current Range: 0 to 10 VDC (single-ended)
Data Format: 16-bit integer (2’s complement)
Accuracy:
• ±0.1%, FSR @ 25°C
• ±0.3%, FSR @ 0°C, 60°C
Input Impedance: 500K ohms
Conversion Time: 4 ms for all channels
Power Consumption: Max. 150 mA @ 5 VDC
Isolation: I/O to logic (photocoupler isolation)
Wiring: I/O cable max. AWG14