Datasheet
www.moxa.com
2
Parity None, Even, Odd, Space, Mark
Stop Bits 1, 2
Flow Control DTR/DSR, RTS/CTS
RS-485 Data Direction Control ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485 120 ohms
Isolation 2 kV (I models)
Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
Configuration Options MGate Manager
Industrial Protocols Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave, PROFIBUS DP-V0 Slave
Modbus RTU/ASCII
Mode Master, Slave
Functions Supported 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. No. of Commands 100
Input Data Size 7744 bytes
Output Data Size 7744 bytes
PROFIBUS Interface
Industrial Protocols PROFIBUS DP
No. of Ports 1
Connector DB9 female
Baudrate 9600 bps to 12 Mbps
Isolation 2 kV (built-in)
Signals PROFIBUS D+, PROFIBUS D-, RTS, Signal Common, 5V
PROFIBUS
Rotary Switch PROFIBUS addresses 0-99 (addresses 100-125 supported through software
configuration)
Mode DP-V0 Slave
Max. No. of Master Connections 1
Max. No. of PROFIBUS I/O Modules 24 per page
Max. No. of PROFIBUS Pages 32