User`s manual

ioLogik E2260 User’s Manual Modbus/TCP Address Mappings
B-4
Reference Address Data Type Description
40017 0x0010 1 word CH0 DO Pulse Output High Signal Width – Hi Word
<RW> 0~4294967295
40018 0x0011 1 word CH0 DO Pulse Output High Signal Width – Lo Word
<RW> 0~4294967295
40019 0x0012 1 word CH1 DO Pulse Output High Signal Width – Hi Word
40020 0x0013 1 word CH1 DO Pulse Output High Signal Width – Lo Word
40021 0x0014 1 word CH2 DO Pulse Output High Signal Width – Hi Word
40022 0x0015 1 word CH2 DO Pulse Output High Signal Width – Lo Word
40023 0x0016 1 word CH3 DO Pulse Output High Signal Width – Hi Word
40024 0x0017 1 word CH3 DO Pulse Output High Signal Width – Lo Word
40025 0x0018 1 word CH0 DO Operation Mode
<RW> 0=DO Mode, 1=Pulse Output Mode
40026 0x0019 1 word CH1 DO Operation Mode
40027 0x001A 1 word CH2 DO Operation Mode
40028 0x001B 1 word CH3 DO Operation Mode
40029 0x001C 1 word CH0 RTD Engineering Unit
0=Ohm, 1=Celsius, 2=Fahrenheit
40030 0x001D 1 word CH1 RTD Engineering Unit
40031 0x001E 1 word CH2 RTD Engineering Unit
40032 0x001F 1 word CH3 RTD Engineering Unit
40033 0x0020 1 word CH4 RTD Engineering Unit
40034 0x0021 1 word CH5 RTD Engineering Unit
40035 0x0022 1 word Virtual CH6 RTD Engineering Unit
1=Celsius, 2=Fahrenheit
40036 0x0023 1 word Virtual CH7 RTD Engineering Unit
40037 0x0024 1 word Virtual CH8 RTD Engineering Unit
40038 0x0025 1 word Virtual CH9 RTD Engineering Unit
40039 0x0026 1 word Virtual CH10 RTD Engineering Unit
40040 0x0027 1 word Virtual CH11 RTD Engineering Unit
40041 0x0028 1 word CH0 RTD Sensor Type
0=PT50
1=PT100
2=PT200
3=PT500
4=PT1000
5=JPT100
6=JPT200
7=JPT500
8=JPT1000
9=NI100
10=NI200
11=NI500
12=NI1000
13=NI120
14=310 Ohm
15=620 Ohm
16=1250 Ohm
17=2500 Ohm
40042 0x0029 1 word CH1 RTD Sensor Type