User`s manual

ioLogik E2260 User’s Manual Modbus/TCP Address Mappings
B-2
Reference Address Data Type Description
00032 0x001F 1 bit CH1 DO Status
00033 0x0020 1 bit CH2 DO Status
00034 0x0021 1 bit CH3 DO Status
00035 0x0022 1 bit CH0 DO Power-On Status
<RW> 0=OFF, 1=ON
00036 0x0023 1 bit CH1 DO Power-On Status
00037 0x0024 1 bit CH2 DO Power-On Status
00038 0x0025 1 bit CH3 DO Power-On Status
00039 0x0026 1 bit CH0 DO Safe Status
<RW> 0=OFF, 1=ON
00040 0x0027 1 bit CH1 DO Safe Status
00041 0x0028 1 bit CH2 DO Safe Status
00042 0x0029 1 bit CH3 DO Safe Status
00043 0x002A 1 bit CH0 DO Pulse Output Status
<RW> 0=Stop, 1=Start
00044 0x002B 1 bit CH1 DO Pulse Output Status
00045 0x002C 1 bit CH2 DO Pulse Output Status
00046 0x002D 1 bit CH3 DO Pulse Output Status
00047 0x002E 1 bit CH0 DO Power-On Pulse Output Status
<RW> 0=Stop, 1=Start
00048 0x002F 1 bit CH1 DO Power-On Pulse Output Status
00049 0x0030 1 bit CH2 DO Power-On Pulse Output Status
00050 0x0031 1 bit CH3 DO Power-On Pulse Output Status
00051 0x0032 1 bit CH0 DO Safe Mode Pulse Output Status
<RW> 0=Stop, 1=Start
00052 0x0033 1 bit CH1 DO Safe Mode Pulse Output Status
00053 0x0034 1 bit CH2 DO Safe Mode Pulse Output Status
00054 0x0035 1 bit CH3 DO Safe Mode Pulse Output Status
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 1 word CH0 RTD Value
<R> 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
30002 0x0001 1 word CH1 RTD Value
30003 0x0002 1 word CH2 RTD Value
30004 0x0003 1 word CH3 RTD Value
30005 0x0004 1 word CH4 RTD Value
30006 0x0005 1 word CH5 RTD Value
30007 0x0006 1 word Virtual CH6 RTD Value
<R> 0~65535, Unit:0.1 (Celsius, Fahrenheit)
30008 0x0007 1 word Virtual CH7 RTD Value
30009 0x0008 1 word Virtual CH8 RTD Value
30010 0x0009 1 word Virtual CH9 RTD Value
30011 0x000A 1 word Virtual CH10 RTD Value
30012 0x000B 1 word Virtual CH11 RTD Value
30013 0x000C 1 word CH0 RTD Minimum Value
<R> 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)