User`s manual
ioLogik E2260 User’s Manual Using the Web Console
4-5
The following table is a list of supported sensor types and ranges.
Sensor Type Degree Count
PT50, 0.00385 -200 to 850°C -2000 to 8500
PT100, 0.00385 -200 to 850°C -2000 to 8500
PT200, 0.00385 -200 to 850°C -2000 to 8500
PT500, 0.00385 -200 to 850°C -2000 to 8500
PT1000, 0.00385 -200 to 350°C -2000 to 3500
JPT100, 0.003916 -200 to 640°C -2000 to 6400
JPT200, 0.003916 -200 to 640°C -2000 to 6400
JPT500, 0.003916 -200 to 640°C -2000 to 6400
JPT1000, 0.003916 -200 to 350°C -2000 to 3500
Res. 100 m 1 to 2200 10 to 22000
Res. 50 m 1 to 1250 20 to 25000
Res. 20 m 1 to 620 50 to 31000
Res. 10 m 1 to 310 100 to 31000
Ni100, 0.00618 -60 to 250°C -600 to 2500
Ni200, 0.00618 -60 to 250°C -600 to 2500
Ni500, 0.00618 -60 to 250°C -600 to 2500
Ni1000, 0.00618 -60 to 180°C -600 to 1800
Ni120, 0.00672 -80 to 260°C -800 to 2600
Channels 6 through 11 are virtual channels. You can click on a virtual channel to configure
whether it will return current averages or deviations for the specified physical channels (RTD-00
through RTD-05).
DO Channels
On the DO Channels page, you may configure each DO (digital output) channel by clicking on the
channel. DO Channels can operate in DO mode or Pulse Output mode. In DO mode, output is
either on or off. In Pulse Output mode, a configurable square wave is generated.