ioLogik E2260 User’s Manual Utilities
3-19
Active Tags Tab
When logged in as an administrator, fill in the IP address in the Active Tags tab to configure
Active OPC Address and Port settings. ioLogik Active Ethernet I/O can support up to 5 IPs at the
same time. The Active OPC Server Address can be filled in using the IP address. The default port
number is 9900. The port number should be the same as the setting in Active OPC Server’s
“Active Tag Listen Port”. After the OPC setting and Channel Tags have been configured as desired,
click Create Tags. The ioLogik Active Ethernet I/O will reboot in order for the settings to take
effect.
The Heartbeat Interval is the time between each instance Active OPC server is informed that
ioLogik is still working. The tags for Analog Value, such as AI, AO, RTD, TC, are synchronized
with pre-defined percentages that are filled in the On Change column. The updated DI/DO/Relay
tags can be synchronized by changing the status. If counter mode is used, Advanced Settings
allows you to synchronize time by 100 to 60,000 ms. Please refer to the Active OPC Server section
for more details about how to use Active OPC server.
These Tags depend
on the model.