Datasheet
2
www.moxa.com
info@moxa.com
Remote I/O
Push Technology for Events and Alarms
The ioLogik E2200 series is designed for use with the Moxa’s
MX-AOPC UA server. When used with MX-AOPC UA Server, the E2200
is upgraded to use active push communications when communicating
state changes and/or events to the SCADA. Unlike a polling system,
when using a push architecture for communications with the SCADA
messages will only be delivered when state changes or configured
events occur. Active messaging thus allows for big increases in data
acquisition and control throughput while also delivering big reductions
in network overhead.
ioLogik E2210 Specifications
Inputs and Outputs
Digital Inputs: 12 channels
Digital Outputs: 8 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Common Type: 12 points per COM
Counter Frequency: 900 Hz
Digital Filtering Time Interval: Software Configurable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Power Consumption: 203 mA @ 24 VDC
MTBF (mean time between failures)
Time: 213,673 hrs
Database: Telcordia (Bellcore)
ioLogik E2212 Specifications
Inputs and Outputs
Digital Inputs: 8 channels
Digital Outputs: 8 channels
Configurable DI/Os: 4 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• OFF: 10 to 30 VDC
Common Type: 6 points per COM
Counter Frequency: 900 Hz
Digital Filtering Time Interval: Software Configurable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @650 mA)
Over-temperature Shutdown: 175°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Power Consumption: 136 mA @ 24 VDC
MTBF (mean time between failures)
Time: 217,722 hrs
Database: Telcordia (Bellcore)