Datasheet

www.moxa.com
2
Push Technology for Events and Alarms
When used with MX-AOPC UA Server, devices can use active push
communications when communicating changes in state and/or
events to a SCADA system. Unlike a polling system, when using a
push architecture for communications with a SCADA system,
messages will only be delivered when changes in state or configured
events occur, resulting in higher accuracy and lower amounts of data
that need to be transferred.
Specifications
Control Logic
Language Click&Go
Input/Output Interface
Analog Input Channels ioLogik E2240 Series: 8
ioLogik E2242 Series: 4
Analog Output Channels ioLogik E2240 Series: 2
Configurable DIO Channels (by software) ioLogik E2212 Series: 4
ioLogik E2242 Series: 12
Digital Input Channels ioLogik E2210 Series: 12
ioLogik E2212 Series: 8
ioLogik E2214 Series: 6
Digital Output Channels ioLogik E2210/E2212 Series: 8
ioLogik E2260/E2262 Series: 4
Relay Channels ioLogik E2214 Series: 6
RTD Channels ioLogik E2260 Series: 6
Thermocouple Channels ioLogik E2262 Series: 8
Buttons Reset button
Isolation 3k VDC or 2k Vrms
Rotary Switch 0 to 9
Digital Inputs
Connector Screw-fastened Euroblock terminal
Counter Frequency 900 Hz
Digital Filtering Time Interval Software configurable
Dry Contact On: short to GND
Off: open
I/O Mode DI or event counter
Points per COM ioLogik E2210 Series: 12 channels
ioLogik E2212/E2242 Series: 6 channels
ioLogik E2214 Series: 3 channels