Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 250 Hz, power off storage
Relay Output
Type: Form A (N.O.) relay outputs, 5A
Contact Rating: 5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC
Inductance Load: 2 A
Resistance Load: 5 A
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (Max.)
Initial Insulation Resistance: 1G min. @ 500 VDC
Expected Life: 100,000 times (Typical)
Initial Contact Resistance: 30 milli-ohms (Max.)
Pulse Output: 0.3 Hz at rated load
MTBF (meantime between failures)
Time: 808,744 hrs
Database: Telcordia (Bellcore)
ioLogik E1240
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 VDC, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Sampling Rate (all channels): 12 samples/sec
Input Impedance: 10M ohms (minimum)
Built-in Resistor for Current Input: 120 ohms
MTBF (meantime between failures)
Time: 474,053 hrs
Database: Telcordia (Bellcore)
ioLogik E1241
Analog Output
Resolution: 12 bits
Output Range: 0 to 10 VDC, 4 to 20 mA
Voltage Output: 10 mA (Max.)
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Load Resistor:
• Internal power: 400 ohms
• External 24V power: 1000 ohms
MTBF (meantime between failures)
Time: 888,656 hrs
Database: Telcordia (Bellcore)