User`s manual

ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-10
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
10001 0x0000 1 bit
CH0 DI Value0=OFF1=ON (Read only)
10002 0x0001 1 bit
CH1 DI Value0=OFF1=ON (Read only)
10003 0x0002 1 bit
CH2 DI Value0=OFF1=ON (Read only)
10004 0x0003 1 bit
CH3 DI Value0=OFF1=ON (Read only)
10005 0x0004 1 bit
CH4 DI Value0=OFF1=ON (Read only)
10006 0x0005 1 bit
CH5 DI Value0=OFF1=ON (Read only)
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 2 word CH0 Read AO Scaling Value (float)
30002 0x0001 2 word CH1 Read AO Scaling Value (float)
30003 0x0002 2 word CH2 Read AO Scaling Value (float)
30004 0x0003 2 word CH3 Read AO Scaling Value (float)
30017 0x0010 1 word CH0 DI Counter Value Hi- Word (Read only)
30018 0x0011 1 word CH0 DI Counter Value Lo- Word (Read only)
30019 0x0012 1 word CH1 DI Counter Value Hi- Word (Read only)
30020 0x0013 1 word CH1 DI Counter Value Lo- Word (Read only)
30021 0x0014 1 word CH2 DI Counter Value Hi- Word (Read only)
30022 0x0015 1 word CH2 DI Counter Value Lo- Word (Read only)
30023 0x0016 1 word CH3 DI Counter Value Hi- Word (Read only)
30024 0x0017 1 word CH3 DI Counter Value Lo- Word (Read only)
30025 0x0018 1 word CH4 DI Counter Value Hi- Word (Read only)
30026 0x0019 1 word CH4 DI Counter Value Lo- Word (Read only)
30027 0x001A 1 word CH5 DI Counter Value Hi- Word (Read only)
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
30049 0x0030 1 word DI Value (Ch0~5)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
………
Bit5 = Ch5 DI Value (0=OFF, 1=ON)
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
41025 0x0400 1 word CH0 AO RAW Value
41026 0x0401 1 word CH1 AO RAW Value
41027 0x0402 1 word CH2 AO RAW Value
41028 0x0403 1 word CH3 AO RAW Value
40033 0x0020 1 word DO all Value (Ch0~5)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
………
Bit5 = Ch5 DO Value (0=OFF, 1=ON)