Datasheet

www.moxa.com
5
Note: 24 V of external power required when loading exceeds 1000 ohms
Output Range 0 to 10 VDC
4 to 20 mA
Resolution 12-bit
RTDs
Accuracy ioLogik E1260:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
ioLogik E1260-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Connector Screw-fastened Euroblock terminal
Input Connection 2- or 3-wire
Input Impedance 625 kilo-ohms (min.)
Sensor Type PT1000 (-200 to 350°C)
PT50, PT100, PT200, PT500 (-200 to 850°C)
Resistance Type 310, 620, 1250, and 2200 ohms
Resolution 0.1°C or 0.1 ohms
Sampling Rate ioLogik E1260: 12 samples/sec per module (shared between up to 6 channels)
4
Thermocouples
Millivolt Accuracy ioLogik E1262:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
ioLogik E1262-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Connector Screw-fastened Euroblock terminal
TC Accuracy Types J, T, E, S, B: ±5°C
Types K, R, N: ±8°C
CJC Accuracy ±0.5°C @ 25°C
±1.5°C @ -40 to 75°C
Input Impedance 10 mega-ohms (min.)
Millivolt Type ±19.532 mV
±39.062 mV
±78.126 mV
Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power
on)
Resolution 16 bits
Sampling Rate ioLogik E1262: 12 samples/sec per module (shared between up to 8 channels)
4
Sensor Type J, K, T, E, R, S, B, N
4. If N channels are enabled, the sampling rate for each enabled channel = 12/N samples/sec.