Datasheet

www.moxa.com
6
Installation DIN-rail mounting, Wall mounting (with optional kit)
Wiring I/O cable, 16 to 26 AWG
Power cable, 12 to 24 AWG
Environmental Limits
Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
HSPA/WL1 -T models: -30 to 70°C (-22 to 158°F)
ioLogik 2512-T/2542-T: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude 2000 m
Standards and Certifications
EMC EN 61000-6-2/-6-4
EMI CISPR 32, FCC Part 15B Class A
EMS All models:
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-6 CS: 3 V
IEC 61000-4-8
ioLogik 2500 Series:
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-5 Surge: Power: 1 kV
ioLogik 2500 Series -HSPA/-WL1 models:
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-5 Surge: Power: 2 kV
Vibration IEC 60068-2-6
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Hazardous Locations ATEX, Class I Division 2
Safety UL 508
Radio EN 301 489-1/17, NCC (-WL models)
Radio Frequency EN 301 908, EN 301 489-24, EN 301 511
WLAN Standards EN 300328
EN 301893
Declaration
Green Product RoHS, CRoHS, WEEE
MTBF
Time ioLogik 2512 Series: 467,032 hrs
ioLogik 2542 Series: 375,439 hrs
ioLogik 2512-HSPA Series: 378,154 hrs
ioLogik 2542-HSPA Series: 378,154 hrs
ioLogik 2512-WL1 Series: 400,469 hrs
ioLogik 2542-WL1 Series: 331,222 hrs
Standards Telcordia SR332