Data Completeness with Local Storage Data Logging
The ioLogik 2500 supports microSD cards, turning it into a powerful data logger for storing valuable data. Important data from field sites can be
accessed remotely by different systems via an FTP, and the ioLogik's data completeness function enables real-time monitoring of data through
MX-AOPC UA Suite when the network goes down unexpectedly.
Remote Access Cellular I/O via Cellular Network
Most carriers provide dynamic and private IP address SIM cards, and
although private IP cards are cheaper, they cannot be used to provide
direct access to the cloud. Moxa’s Cellular Data Access software
enables this type of connection by establishing a special data route
between the cellular models and the cloud.
Only one public IP address is needed to use Moxa’s Cellular Data
Access software, allowing you to easily update internal register
values, change output channel status, and modify the configurations
of devices connected to the device, all through the cloud.
Specifications
Memory
microSD Slot Up to 32 GB (SD 2.0 compatible)
Note: For units operating in extreme temperatures, industrial-grade, wide-temperature
microSD cards are required.
Control Logic
Language Click&Go Plus
Input/Output Interface
Analog Input Channels ioLogik 2542 Series: 4
Digital Input Channels ioLogik 2512 Series: 8
Configurable DIO Channels (by software) ioLogik 2512 Series: 8
ioLogik 2542 Series: 12
Buttons Reset button
Isolation 3k VDC or 2k Vrms
Digital Inputs
Connector Screw-fastened Euroblock terminal
I/O Mode DI or event counter
Sensor Type Dry contact
Wet contact (NPN or PNP)
Dry Contact On: short to GND
Off: open
Wet Contact (DI to COM) On: 10 to 30 VDC
Off: 0 to 3 VDC
Points per COM ioLogik 2512 Series: 8 channels
ioLogik 2542 Series: 6 channels
Counter Frequency 2.5 kHz
Digital Filtering Time Interval Software configurable