User Manual
ioThinx 4510 Series Appendix
A-6
04: INPUT REGISTER
Parameter Description Length Type
diStatusAll DI - DI mode - status (0: OFF, 1: ON) 1 WORD
diCounterOverflowFlagAll DI - Counter mode - overflow flag (0: Normal, 1:
Overflow)
1 WORD
diModeAll
DI - mode (0: DI, 1: Counter)
1
WORD
doModeAll DO - mode (0: DO, 1: Pulse) 1 WORD
45MR-3800 (-T), 8 AIs Registers
01: COIL STATUS
Parameter Description Length Type
aiResetMinValue AI - reset minimum value (1: Reset) 8 BOOL
aiResetMaxValue AI - reset maximum value (1: Reset) 8 BOOL
03: HOLDING REGISTER
Parameter Description Length Type
aiResetMinValueAll AI - reset minimum value (1: Reset) 1 WORD
aiResetMaxValueAll AI - reset maximum value (1: Reset) 1 WORD
04: INPUT REGISTER
Parameter Description Length Type
aiValueRaw AI - raw value 8 WORD
aiValueRawMin AI - minimum raw value 8 WORD
aiValueRawMax AI - maximum raw value 8 WORD
aiValueScaled AI - scaled value 16 REAL
aiValueScaledMin AI - minimum scaled value 16 REAL
aiValueScaledMax AI - maximum scaled value 16 REAL
aiStatus AI - status (0: normal, 1: burnout, 2: over
range, 3. under range)
8 WORD
aiBurnoutValueScaled AI - scaled burnout value 16 REAL
aiMode AI - mode (0: disable, 1: 0-10 V, 2: 0-20 mA, 3:
4-20 mA burnout, 4: 4-20 mA, 5: ±10 V)
8 WORD
45MR-3810 (-T), 8 AIs Registers
01: COIL STATUS
Parameter Description Length Type
aiResetMinValue AI - reset minimum value (1: Reset) 8 BOOL
aiResetMaxValue
AI - reset maximum value (1: Reset)
8
BOOL
03: HOLDING REGISTER
Parameter Description Length Type
aiResetMinValueAll AI - reset minimum value (1: Reset) 1 WORD
aiResetMaxValueAll AI - reset maximum value (1: Reset) 1 WORD