User Manual
ioThinx 4510 Series Software Tools
4-21
DO Mode
Power on Status: The DO status upon powering up (option: ON or OFF).
Safe Mode Status: The DO status when the device is in safe mode (option: ON or OFF).
Power on Delay: The time delay before triggering Power on Status after powering up (unit: sec(s), 0 to
65535).
Pulse Mode
Power on Status: The Pulse status upon powering up (option: ON or OFF).
Safe Mode Status: The Pulse status when the device is in safe mode (option: ON, OFF, or Hold Last).
Power on Delay: The time delay before triggering Power on Status after powering up (unit: sec(s), 0 to
65535).
Pulse Count: The number of pulses per triggering (0 to 4294967295, “0” for continuous pulse output).
On Width/Off Width: The high and low level widths of a pulse (unit: 500μs, 1 to 65535).
NOTE
Not all
DO channels support pulse mode. Refer to the ioThinx 4500 Series (45MR) Modules
datasheet for
detailed
specifications.