User Manual
ioThinx 4510 Series Software Tools
4-5
Module & I/O
The Module & I/O provides information about modules and I/Os status. It also allows you to change the I/O
status.
Module Drop-Down List: It lists all of the I/O modules of this device. Select the specific module for its module
and I/O information.
Locate: Identify the physical location of the module and the module’s status LED will blink green.
DI Channel (DI Mode): It shows the status of this channel. No operation is allowed.
DI Channel (Counter Mode): It shows the status of this channel. Type a value between 0 and 4294967295,
and then click SET to set the current counter value. Click RUN or PAUSE to change the counter status.
DO Channel (DO Mode): It shows the status of this channel. Click ON or OFF to change the DO status.