Installation Guide
Table Of Contents
- EDS-4014 Series Quick Installation Guide
- Package Checklist
- Default Settings
- Panel Views of EDS-4014 Series
- Mounting Dimensions
- DIN-rail Mounting
- Wall Mounting (Optional)
- Wiring Requirements
- Grounding the Moxa EDS Series
- Suggested Wire Type for Wiring Relay Contact (RELAY), Digital Input (DI), and Power Inputs (P1/P2)
- Wiring the Relay Contact
- Wiring the Redundant Power Inputs
- Wiring the Digital Inputs
- Rotating the Power Module
- Communication Connections
- Reset Button
- Turbo Ring DIP Switch Settings
- LED Indicators
- Specifications
- 16 -
Spe cificat ions
I nt e r fa ce
RJ45 Port s
10/ 100/ 1000BaseT(X)
Fiber Port s 100/ 1000BaseSFP
1000/ 2500BaseSFP
Console Por t
RS-232 ( RJ45 )
But t on
Reset but t on
LED I ndicat or s STATE ( S) , FAULT ( F), PWR1 ( P1) , PWR2 ( P2 ),
MSTR/ HEAD ( M/ H) , CPLR/ TAI L ( C/ T) , SYNC
Alarm Cont act
1 nor m ally open elect rom agnet ic relay out put with
curr ent carr ying capacit y of 1 A @ 24 VDC
Digit al I nput
1 isolat ed digit al in put :
+ 13 t o + 30V for st at e “ 1”
-30 t o + 3V for st ate “ 0”
Max. in put cur rent : 8 m A
Pow e r
Pr e- inst alled Power
Module
-LV/ -LV- T m odels: PWR- 100–LV
-HV/ - HV-T m odels: PWR- 105- HV- I
Not e The EDS- 4014 Series support s m odular power
supplies. The model nam es and power param et ers
are det erm ined by the installed power m odule.
For ex am ple:
EDS- 4014- T + PWR- 100- LV = EDS- 4014- LV- T
EDS- 4014- T + PWR- 105- HV- I = EDS- 4014- HV- T
I f y ou install a differ ent pow er m odule, refer t o t he
specificat ions of t he cor responding m odel. For
exam ple, if y ou r eplace the power m odule of t he
EDS- 4014- LV- T with t he PWR-105 -HV- I , refer t o
t he specificat ions of t he EDS-4014 -HV- T.
Rat ed Volt age
-LV/ -LV- T m odels: 12/ 24/ 48 VDC, r edundant dual
input s
-HV/ - HV- T m odels: 110/ 220 VDC/ VAC, single input
Operat ing Voltage
-LV/ -LV- T m odels: 9.6 t o 60 VDC
-HV/ - HV- T m odels: 88 t o 300 VDC, 85 t o 264 VAC
Rat ed Current
-LV/ -LV- T m odels: 12- 48 VDC, 1.50- 0.40 A or 24
VDC, 0.70 A
-HV/ - HV-T m odels: 110- 220 VAC, 50- 60 Hz, 0.30 -
0.20 A or 110 -220 VDC, 0.30- 0.20 A
Power
Consum pt ion
EDS- 4014- 4GS-2QGS- LV( - T) m odels: 12.15 W
EDS- 4014- 4GS- 2QGS- HV(- T) m odels: 14 .44 W
I nrush Current
Max. 0.58 A @ 48 VDC ( 0.1 – 1 m s) ( Applied t o -
LV m odels)
Overload Curr ent
Pr otect ion at I nput
Present
Reverse Polarit y
Pr ot ect ion
Present
Connect ion
2 rem ovable 4- contact t erminal blocks
Ph ysica l Ch ar a cte r ist ics
Housing
Met al, I P40 pr ot ect ion
Dim ension
55 x 140 x 122.5 m m ( 2.17 x 5.51 x 4.82 in)
Weight
846 g ( 1.87 lb)