Installation guide

6
You should also pay attention to the following items:
y Use separate paths to route wiring for power and devices. If power wiring
and device wiring paths must cross, make sure the wires are perpendicular
at the intersection point.
NOTE: Do not run signal or communications wiring and power wiring in
the same wire conduit. To avoid interference, wires with different signal
characteristics should be routed separately.
y You can use the type of signal transmitted through a wire to determine
which wires should be kept separate. The rule of thumb is that wiring with
similar electrical characteristics can be bundled together.
y Keep input wiring and output wiring separate.
y It is strongly advised that you label wiring to all devices in the system when
necessary.
Grounding Moxa AWK-6222
Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the
ground screw to the grounding surface prior to connecting devices.
ATTENTION
This product is intended to be mounted to a well-grounded
mounting surface, such as a metal panel. There must be no
potential difference between two ground potentials, otherwise
there is a risk that the device could be destroyed.
Wiring the Redundant Power Inputs
The AWK-6222 must be connected to a power-over-Ethernet (PoE) IEEE
802.3af compliant power source or an IEC60950 compliant limited power
source. When AWK-6222 is powered via DC power, the M12 A-coding
connector on the bottom panel is used for the AWK-6222’s two redundant
inputs. The pin assignment is shown below:
1
43
2
5
Pin Power Input
1 V1+
2 V2+
3 V1-
4 V2-
5 GND