User`s manual

W406 Hardware User’s Manual Introduction
Digital Input Levels for Dry Contacts:
• Logic level 0: Close to GND
• Logic level 1: Open
Digital Input Levels for Wet Contacts:
• Logic level 0: +3 V max.
• Logic level 1: +10 V to +30 V (COM to DI)
Connector Type: 10-pin screw terminal block
Isolation: 3 KV optical isolation
Digital Output
Output Channels: 4, sink type
Output Current: Max. 200 mA per channel
On-state Voltage: 24 VDC nominal, open collector to 30 V
Connector Type: 9-pin screw terminal block
Isolation: 3 KV optical isolation
LEDs
System: Ready, Storage
LAN: 10M/Link, 100M/Link (on connector)
Cellular: Cellular Enable, Signal Strength (5 LEDs)
Serial: TxD, RxD
Switches and Buttons
Reset Button: Supports “Reset to Factory Default”
Cellular Reset Button: Supports cellular reset function
Physical Characteristics
Housing: Aluminum (1 mm)
Weight: 1 kg
Dimensions: (without ears or antenna)
144 x 119 x 40 mm (5.7 x 4.7 x 1.6 in)
Mounting: DIN-rail, wall (requires optional wall mount kit)
Antenna Length: 85 mm
Environmental Limits
Operating Temperature:
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 70°C (-40 to 158°F)
Operating Humidity: 5 to 95% RH
Storage Temperature:
Standard Models: -20 to 80°C (-4 to 176°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Anti-Vibration: 2g @ IEC-68-2-6, sine wave, 5-500 Hz, 1 Oct./min, 1 hr/axis
1-5