User`s manual

ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-20
E1260 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
31537 0x0600 1 word CH0 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31538 0x0601 1 word CH1 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31539 0x0602 1 word CH2 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31540 0x0603 1 word CH3 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31541 0x0604 1 word CH4 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31542 0x0605 1 word CH5 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
E1262 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
32049 0x0800 1 word CH0 TC Minimum Value Hi Word
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32050 0x0801 1 word CH0 TC Minimum Value Lo Word
Hi+Lo Range: 0~4294967295
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32051 0x0802 1 word CH1 TC Minimum Value Hi Word
32052 0x0803 1 word CH1 TC Minimum Value Lo Word
32053 0x0804 1 word CH2 TC Minimum Value Hi Word
32054 0x0805 1 word CH2 TC Minimum Value Lo Word
32055 0x0806 1 word CH3 TC Minimum Value Hi Word
32056 0x0807 1 word CH3 TC Minimum Value Lo Word
32057 0x0808 1 word CH4 TC Minimum Value Hi Word
32058 0x0809 1 word CH4 TC Minimum Value Lo Word
32059 0x080A 1 word CH5 TC Minimum Value Hi Word
32060 0x080B 1 word CH5 TC Minimum Value Lo Word
32061 0x080C 1 word CH6 TC Minimum Value Hi Word
32062 0x080D 1 word CH6 TC Minimum Value Lo Word
32063 0x080E 1 word CH7 TC Minimum Value Hi Word
32064 0x080F 1 word CH7 TC Minimum Value Lo Word
32065 0x0810 1 word CH8 TC Minimum Value Hi Word
32066 0x0811 1 word CH8 TC Minimum Value Lo Word