User`s manual
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-19
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
30029 0x001C 1 word CH6 DI Counter Value Hi- Word (Read only)
30030 0x001D 1 word CH6 DI Counter Value Lo- Word (Read only)
30031 0x001E 1 word CH7 DI Counter Value Hi- Word (Read only)
30032 0x001F 1 word CH7 DI Counter Value Lo- Word (Read only)
30049 0x0030 1 word DI Value (Ch0~7)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
Bit7 = Ch7 DI Value (0=OFF, 1=ON) ………
Bit8 to 15 = reserved
30513 0x0200 1 word CH0 Read AI RAW Value
30514 0x0201 1 word CH1 Read AI RAW Value
30515 0x0202 1 word CH2 Read AI RAW Value
30516 0x0203 1 word CH3 Read AI RAW Value
30521 0x0208 2 word CH0 Read AI Scaling Value (float)
30522 0x0209 2 word CH1 Read AI Scaling Value (float)
30523 0x020A 2 word CH2 Read AI Scaling Value (float)
30524 0x020B 2 word CH3 Read AI Scaling Value (float)
30577 0x0240 1 word Read AI 0 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
30578 0x0241 1 word Read AI 1 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
30579 0x0242 1 word Read AI 2 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
30580 0x0243 1 word Read AI 3 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
40033 0x0020 1 word DO all Value (Ch0~3)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
Bit3 = Ch3 DO Value (0=OFF, 1=ON) ………
Bit4 to 15 = reserved
40545 0x0220 1 word CH0 AI 0 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40546 0x0221 1 word CH0 AI 1 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40547 0x0222 1 word CH0 AI 2 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40548 0x0223 1 word CH0 AI 3 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40561 0x0230 2 word CH AI 0 BO Value (floating point)
40563 0x0232 2 word CH AI 1 BO Value (floating point)
40565 0x0234 2 word CH AI 2 BO Value (floating point)