User`s manual
ioLogik E1200 Series  Modbus/TCP Default Address Mappings 
A-16 
E1241 Modbus Mapping 
0xxxx Read/Write Coils (Functions 1, 5, 15) 
Reference  Address  Data Type  Description 
04097  0x1000  1Bit  CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE 
04098  0x1001  1Bit  CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE 
04099  0x1002  1Bit  CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE 
04100  0x1003  1Bit  CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE 
04113  0x1010  1Bit  CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode 
04114  0x1011  1Bit  CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode 
04115  0x1012  1Bit  CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode 
04116  0x1013  1Bit  CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode 
04129  0x1020  1Bit  CH0 AO Clear P2P Output Safe Status   
Write: 1= clear status 
Read: always zero 
04130  0x1021  1Bit  CH1 AO Clear P2P Output Safe Status   
Write: 1= clear status 
Read: always zero 
04131  0x1022  1Bit  CH2 AO Clear P2P Output Safe Status   
Write: 1= clear status 
Read: always zero 
04132  0x1023  1Bit  CH3 AO Clear P2P Output Safe Status   
Write: 1= clear status 
Read: always zero 
3xxxx Read Only Registers (Function 4) 
Reference  Address  Data Type  Description 
30001  0x0000  2 word  CH0 Read AO Scaling Value (float) 
30002  0x0001  2 word  CH1 Read AO Scaling Value (float) 
30003  0x0002  2 word  CH2 Read AO Scaling Value (float) 
30004  0x0003  2 word  CH3 Read AO Scaling Value (float) 
4xxxx Read/Write Registers (Functions 3, 6, 16) 
Reference  Address  Data Type  Description 
41025  0x0400  1 word  CH0 AO RAW Value 
41026  0x0401  1 word  CH1 AO RAW Value 
41027  0x0402  1 word  CH2 AO RAW Value 
41028  0x0403  1 word  CH3 AO RAW Value 