User`s manual

ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-16
E1241 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
04097 0x1000 1Bit CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04099 0x1002 1Bit CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04129 0x1020 1Bit CH0 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 2 word CH0 Read AO Scaling Value (float)
30002 0x0001 2 word CH1 Read AO Scaling Value (float)
30003 0x0002 2 word CH2 Read AO Scaling Value (float)
30004 0x0003 2 word CH3 Read AO Scaling Value (float)
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
41025 0x0400 1 word CH0 AO RAW Value
41026 0x0401 1 word CH1 AO RAW Value
41027 0x0402 1 word CH2 AO RAW Value
41028 0x0403 1 word CH3 AO RAW Value