User`s manual

ioLogik E1200 Series Using the Web Console
3-13
AI Input Range
AI Input: Voltage Mode: V (Jumper Settings (DIO and AI))
There is only one default analog ā€œvoltageā€ input range: [0-10V]
AI Input: Current Mode: mA (Jumper Settings (DIO and AI))
There are three modes in the analog ā€œcurrentā€ input range: [4-20 mA], [0-20 mA],[4-20 mA (burnout)]
NOTE
only
[0-10 V] and [4-20 mA] supports peer to peer networking.
AI Input: Current Mode
Burnout mode can indicate if the current analog input has burnt out.
The 4-20 mA burnout mode is defined in the diagram in the following
Users can define burnout values (BO, default 2mA) for selected ranges. When input values are in the burnout
range, raw data will register as 0000h to indicate analog input burnout. The definition of raw data is as follows: