User`s manual

ioLogik E1200 Series Using the Web Console
3-10
DO Channels
On the I/O Setting: DO (Digital Output) Channels page; You can configure each DO channel by clicking on the
channel.
DO Channels can operate in DO mode and is either on or off.
Or in Pulse Output mode, you can specify the ON Width and OFF width to generate a square wave.
Pulse Width unit = 1 ms, range = 1-65535
When configuring individual channels, if the Power On Setting is selected the Pulse Output will start as soon
as the ioLogik E1200 is powered on; if the Safe Status Setting is selected, the Pulse Output will start only
once the E1200 has entered Safe Status mode; In contrast, When neither of these setting is selected and
Pulse Start field is selected, the ioLogik E1200 will automatically stop the Pulse Output when either ioLogik
E1200 is Powered On or when ioLogik E1200 entered into Safe Status mode. (Note* that Safe Status is
controlled by the Communication Watchdog under General Setting, which is disabled by default. If the
Communication Watchdog is disabled, the ioLogik E1200 will never enter Safe Mode and your Safe Status
settings will have no effect.)