User`s manual
ioLogik E1200 Series Using the Web Console
3-8
I/O Settings
DI Channels
The status of each DI (digital input) channel appears on the I/O Setting: DI Channels page.
You can also configure each channel’s digital input mode and parameters by clicking on the channel. DI
Channels can operate in DI mode or Event Counter mode.
You activate the Event Counter mode by selecting the Counter Start field and configure the Counter
Trigger to be either “Lo to Hi,” “Hi to Lo,” or “Both”. When the Counter Start field is not selected you can
still activate the counter by using Modbus command.
Note* Make sure that the Counter Filter is not set to 0; otherwise, the counter will never be activated.
When configuring individual channels, if the Power On Setting is selected the counter will start as soon as the
ioLogik E1200 is powered on; if the Safe Status Setting is selected, the counter will start only once the E1200
has entered Safe Status mode; In contrast, When neither of these setting is selected and “Counter Start”
setting is, the ioLogik E1200 will automatically stop the Counter when either ioLogik E1200 is Powered On or
when it entered into Safe Status mode. (Note* that Safe Status is controlled by the Communication Watchdog
under General Setting, which is disabled by default. If the Communication Watchdog is disabled, the ioLogik
E1200 will never enter Safe Mode and your Safe Status settings will have no effect.)
By selecting Save Status on Power Failure field, the ioLogik E1200 will automatically save the counter value
when there is a power failure. To reset the Counter, you will select Reset Counter field and then click on the
Submit button.