User`s manual
ioLogik E1200 Series Introduction
1-10
ioLogik E1214
Inputs and Outputs
Digital Inputs:
6 channels
Relay Outputs:
6 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (NPN, DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Wet Contact (PNP, DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type:
6 points per COM
Isolation:
3K VDC or 2K Vrms
Counter Frequency:
250 Hz, power off storage
Digital Filtering Time Interval:
Software selectable
Relay Output
Type:
Form A (N.O.) power relay
Contact Current Rating:
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage:
500 VAC
Relay On/Off Time:
1500 ms (Max.)
Initial Insulation Resistance:
1000 M ohms (min.) @ 500 VDC
Mechanical Endurance:
5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance:
100 m ohms (max.)
Pulse Output:
0.3 Hz at rated load
Isolation:
3K VDC or 2K Vrms
Note: Ambient humidity must be non
-
condensing and remain between 5 and 95%. The relays of the ioLogik
E1214 may malfunction when operating in condensing environments below 0° Celsius.
Power Requirements
Power Consumption:
188 mA @ 24 VDC
MTBF (mean time between failures)
Time:
808,744 hrs
Database:
Telcordia (Bellcore)