User`s manual
UC-8410/8416/8418/8430 Hardware User's Manual Introduction
1-4
Connector Type: 10-pin screw terminal block (4 points, COM, GND)
Isolation: 3 KV optical isolation
Digital Output
Output Channels: sink type
• UC-8410/8416/UC8430: 4 channels
• UC-8418: 12 channels
Output Current: Max. 200 mA per channel
On-state Voltage: 24 VDC nominal, open collector to 30 V
Connector Type: 10-pin screw terminal block (4 points, GND)
Isolation: 3 KV optical isolation
CANbus Communication (UC-8418 only)
Interface: Dual optically isolated CAN2.0A/2.0B compliant ports
CAN Controller: Phillips SJA1000T
Signals: CAN-H, CAN-L
Isolation: 2 KV digital isolation
Speed: 10 Kbps to 1 Mbps
Connector Type: DB9 male
LEDs
System: Power, Ready, Storage, Battery for SRAM
LAN: 10M/Link x 2, 100M/Link x 2 (on connector)
Serial: TxD x 8, RxD x 8
Reset Button: Supports "Reset to Factory Default"
Physical Characteristics
Housing: SECC sheet metal (1 mm)
Weight: 1 kg
Dimensions:
UC-8410: 200 x 37 x 120 mm (7.87 x 1.46 x 4.72 in)
UC-8416/8418: 200 x 57 x 120 mm (7.87 x 2.24 x 4.72 in)
Mounting: DIN-Rail, wall
Environmental Limits
Operating Temperature:
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Operating Humidity: 5 to 95% RH
Storage Temperature:
Standard Models: -20 to 75°C (-4 to 167°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Anti-vibration: 2 g rms @ IEC-68-2-34, random wave, 5-500 Hz, 1 hr per axis
Anti-shock: 20 g @ IEC-68-2-27, half sine wave, 11 ms
Power Requirements
Input Voltage: 12 to 48 VDC (3-pin terminal block)
Power Consumption: 15 W
• 310 mA @ 48 VDC
• 625 mA @ 24 VDC
• 1350 mA @ 12 VDC
Regulatory Approvals
EMC: CE (EN55022 Class B, EN55024-4-2, EN55024-4-3,
EN55024-4-4), FCC (Part 15 Subpart B, Class B)
Safety: UL/cUL (UL60950-1), CCC (GB9254, GB 17625.1), LVD (EN60950)
Reliability
Alert Tools: Built-in buzzer and RTC (real-time clock)
Automatic Reboot Trigger: Built-in WDT (watchdog timer)