UC-7400 Plus User’s Manual Hardware Connection Description
You should also observe the following common wiring rules:
y Use separate paths to route wiring for power and devices. If power wiring and device wiring
paths must cross, make sure the wires are perpendicular at the intersection point.
NOTE: Do not run signal or communication wiring and power wiring in the same wire conduit.
To avoid interference, wires with different signal characteristics should be routed separately.
y You can use the type of signal transmitted through a wire to determine which wires should be
kept separate. The rule of thumb is that wiring that shares similar electrical characteristics can
be bundled together.
y Keep input wiring and output wiring separate.
y Where necessary, it is strongly advised that you label wiring to all devices in the system.
Connecting the Power
Connect the 12 to 48 VDC power line to the UC-7400 Plus’s terminal block. If the power is
properly supplied, the Ready LED will illuminate with a solid green color after 30 to 60 seconds
have passed.
Grounding the UC-7400 Plus
Grounding and wire routing helps limit the effects of noise due to electromagnetic interference
(EMI). Run the ground connection from the ground screw to the grounding surface prior to
connecting devices.
ATTENTION
This product is intended to be mounted to a well-grounded mounting surface, such as a metal
panel.
SG
DC 12-48V
SG: The Shielded Ground (sometimes called Protected Ground) contact is the
left most contact of the 3-pin power terminal block connector when
viewed from the angle shown here. Connect the SG wire to an
appropriate grounded metal surface.
3-4