Specifications
Industrial Networking Solutions
4-19
info@moxa.com
www.moxa.com
Industry-specific Ethernet Switches >
Introduction to IEC 61850-3 Rackmount Ethernet Switches
4
Model
PT-7828
28 4 24 ---
√ √ √
P
√ √ √ √ √ √ √ √
---
√ √ √
PT-7728
28 4 24 ---
√ √ √
P ---
√ √ √ √ √ √ √
---
√ √ √
PT-7710
10 2 8 ---
√ √ √
P ---
√ √ √ √ √ √ √ √ √
---
√
PT-7324
24 2 22 ---
√ √ √
P --- --- --- --- --- --- --- ---
√ √
--- ---
IKS-6726
26 2 24 --- ---
√ √
P ---
√ √ √ √ √ √ √
---
√ √ √
IKS-6726-PoE
26 2 8 16 ---
√ √
P ---
√ √ √ √ √ √ √
---
√ √ √
IKS-6324
24 2 22 --- ---
√ √
P --- --- --- --- --- --- --- --- --- --- --- ---
Total Number of Ports
Gigabit Ethernet
(10/100/1000 Mbps)
Fast Ethernet
(10/100 Mbps)
PoE, Fast Ethernet
(10/100 Mbps)
IEC 61850-3, IEEE 1613
NEMA TS2
EN50155/EN50121-4
DNV/GL
Layer 3 Switching
Turbo Ring and RSTP/STP
IGMP snooping/GMRP
Port Trunking
IEEE 802.1X/HTTPS/SSH
Port Lock
SNMP/RMON
802.1Q VLAN
Port-based VLAN
QoS
Isolated Redundant Power
ABC-01*
Comparison Chart for Rackmount Ethernet Switches
Port Interfaces
Certifications
Features
(All products listed support a wide operating temperature range: -40 to 85°C for the PT series, and -40 to 75°C for the IKS series.)
*ABC-01 is an RS-232 RJ45-based automatic backup configurator for managed Ethernet Switches. See page 3-48 for details.
Test NEMA TS2
Temperature
-34 to 74˚C
Humidity
18% to 90% RH, non-condensing
Voltage
120 to 135 VAC @ 57 to 63 Hz
Vibration
0.5 g @ 5 to 30 Hz
Shock
10 g’s for 11 ms
Road Traffic Control System Standard
Railway Control System Standards
NEMA TS2
The National Electrical Manufacturers Association (NEMA) established
the TS1 standard to define technically adequate and safe traffic control
equipment. The TS2 standard was later introduced to address some
drawbacks of the original guidelines. NEMA TS2 defines controllers,
cabinets, and systems more completely than TS1, promotes better
interchangeability, and allows for future expansion. Section 2 contains
the environmental and testing requirements, including guidelines for
temperature, humidity, voltage, vibration, and shock. PT series and IKS
series switches are compliant with the NEMA TS2 traffic control system
standard.
EN50121-4
EN50121-4 defines emission and immunity standards for signaling and
telecommunication apparatus.
EN50155
The complete PT and IKS series are certified according to the EN50155
ensuring safe deployment for railway applications.
= Available P = Pending Note: Please check Moxa’s website for the most up-to-date certification status.
and control functions, on-line processing and regulation, as well as
metering and network communication, must experience no delays or
data loss when exposed to various EMI phenomena.
IEEE 1613
IEEE 1613 is another industry standard that establishes EMI immunity
requirements for networking devices in electric power substations.
Included in this standard are ratings, environmental performance
requirements, and testing requirements for compliant communication
devices.
According to the IEEE 1613 standard, compliant devices may not
experience permanent damage under EMI stress. Two different classes
of devices are defined in the standard according to how EMI stress
affects performance.
Class 1
Compliant devices in this class may experience some data errors,
losses, or delays under EMI stress conditions.
Class 2
Compliant devices in this class must not experience any data errors,
delays, or losses under EMI stress conditions.
The PowerTrans PT series is compliant with IEC 61850-3 and IEEE
1613 certifications specifying a high level of EMC, shock, and vibration
in power substations.