Test Report ------------------------------------------------------------------------------- 30/48
Report No.: M47ET060805 (ETSI EN 301 489)
Training Research Co., Ltd., TEL: 886-2-26935155, Fax: 886-2-26934440
Chapter 7 Surge Immunity Test
Surge Test information:
Test setup: According to EN 61000-4-5
Test levels: (Apply Level 2 and Level 3)
Level Test Field Strength
(kV)
1 0.5
2 1.0
3 2.0
4 4.0
X Special
NOTE: the “X” is an open class. This level may be specified in the product specification.
Test Voltage: DC Power line 0.5 KV
AC Power line Line – Line: 1KV
Line – Ground: 2KV
Line – Line: 0.5KV
Line – Ground: 1KV
Control line 0.5 KV
Signal 1 KV,
0.5KV
Time: 1.2/50µs [Voltage waveform]
8/20µs [Current waveform]
Polarity: Positive
Negative
Connected lines: Power line shielded
Power line non-shielded
Signal & Control line non-shielded
Signal & Control line shielded