Serial Settings
Click on the Serial Settings link on the left side of the screen to display serial settings. Make
necessary changes to the settings and click on submit to validate the modifications.
Port alias
Setting Factory Default Necessity
1 to 15 characters
(E.g., PLC-No.1)
None Optional
Port Alias is specially designed to allow easy identification of the serial devices which are
connected to NE-4100 Series’ serial port.
Serial Parameters
Check the serial communication parameters in your Serial Device’s user’s manual. You should set up
NE-4100’s serial parameters with the same communication parameters used by your serial devices.
Baud rate
Setting Factory Default Necessity
50 bps to 115.2 Kbps 115.2 Kbps Required
NE-4100 supports a baud rate setting from 50 bps to 115.2 Kbps.
Data bits
Setting Factory Default Necessity
5, 6, 7, 8 8 Required
When the user sets Data bits to 5 bits, the stop bits setting will automatically change to 1.5 bits.
Stop bits
Setting Factory Default Necessity
1, 2 1 Required
Stop bits will be set to 1.5 when Data bits is set to 5 bits.
Parity
Setting Factory Default Necessity
None, Even, Odd, Space, Mark None Required