Specifications
4-8
www.moxa.com
info@moxa.com
MGate™ MB3180/3280/3480
4
Industrial Ethernet Gateways
Industrial Ethernet Gateways >
1, 2, and 4-port standard serial-to-Ethernet Modbus gateways
Specifications
Overview
High Density, Cost-effective Gateways
Standard Modbus Network Integration
MGate™ MB3180/3280/3480
The MB3180, MB3280, and MB3480 are standard Modbus gateways
that convert between Modbus TCP and Modbus RTU/ASCII protocols.
Up to 16 simultaneous Modbus TCP masters are supported, with up to
The three standard MGate™ models (MB3180, MB3280, and MB3480)
are designed for easy integration of Modbus TCP and RTU/ASCII
networks. With these models, Modbus serial slave devices can be
seamlessly incorporated into an existing Modbus TCP network, and
The MGate™ MB3000 gateways can effectively connect a high density
of Modbus nodes to the same network. The MB3280 can manage
up to 62 serial slave nodes, and the MB3480 can manage up to 124
serial slave nodes. Each RS-232/422/485 serial port can be configured
31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32
TCP slaves are supported.
Modbus TCP slaves can be made accessible to serial masters. The
MB3180, MB3280, and MB3480 offer features that make network
integration easy, customizable, and compatible with almost any
Modbus network.
individually for Modbus RTU or Modbus ASCII operation and for
different baudrates, allowing both types of networks to be integrated
with Modbus TCP through one Modbus gateway.
› Convert between Modbus TCP and Modbus RTU/ASCII
› 1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
› 16 simultaneous TCP masters with up to 32 simultaneous
requests per master
› Easy hardware setup and conguration
Ethernet Interface
Protocol: Modbus TCP
Number of Ports: 1
Speed: 10/100 Mbps, Auto MDI/MDIX
Connector: 8-pin RJ45
Magnetic Isolation Protection: 1.5 kV (built-in)
Serial Interface
Protocol: Modbus RTU/ASCII Slave/Master
Number of Ports:
MB3180: 1
MB3280: 2
MB3480: 4
Serial Standards: RS-232/422/485, software selectable
Connectors: DB9 male
ESD Protection: 15 kV for all signals
RS-485 Data Direction Control: ADDC® (automatic data direction
control)
Serial Communication Parameters
Data Bits: 7, 8
Stop Bits: 1, 2
Parity: None, Even, Odd, Space, Mark
Flow Control: RTS/CTS, DTR/DSR (RS-232 only)
Baudrate: 50 bps to 921.6 kbps
Serial Signals
RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422: Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w: Data+, Data-, GND
Software
Conguration Options: Web Console, Serial Console, Telnet Console,
Windows Utility
Utilities: MGate Manager for Windows 2000/XP/2003/Vista/Server
2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop:
Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support: Smart Routing, MXview, SNMP v1 (read only)
Physical Characteristics
Housing: Metal, IP30 protection
Weight:
MGate MB3180: 340 g
MGate MB3280: 360 g
MGate MB3480: 740 g