User`s manual

MGate MB3000 User’s Manual Configuring the Modbus Gateway
4-16
Filter Traffic Information
By default, all events are displayed in the traffic monitor window. MGate Manager also allows the
data to be filtered so only the relevant information is displayed. The filter is selected using the
radio buttons and customized using the “Filter info” field, as follows:
Filter Customization Description
All - Show all traffic
Exception only - Show only exceptions
VSID=<virtual slave ID>
(e.g., “VSID=1”)
Show only traffic to and from
the specified “virtual” slave ID
(as assigned in the MGate’s ID
table)
SID only
RSID=<actual slave ID>
(e.g., “RSID=1”)
Show only traffic to and from
the specified “actual” slave ID
(as assigned on the device itself)
IP=<IP address>
(e.g., “IP=192.168.1.2”)
Show only traffic sent from the
specified IP address
Source only
PORT=<MGate serial port number>
(e.g., “PORT=1”)
Show only traffic sent from the
specific serial port on the MGate
Function code only FCODE=<Modbus function code>
(e.g., “FCODE=3”)
Show only traffic for a specific
function code
Save Log to File
To save the data log to a file, click Save. You may retrieve a saved log by clicking Load.