User`s manual

MGate MB3000 User’s Manual Typical Applications
3-3
Modbus TCP Masters with ASCII and RTU Slaves
Link TCP master devices with both ASCII and RTU serial devices simultaneously
When integrating Modbus networks, you may encounter different Modbus serial networks that use
different baudrates or a different protocol. Modbus ASCII might be used by some devices, while
Modbus RTU is used by other devices.
The MGate MB3280 and MB3480 can integrate serial Modbus networks that use different
parameters or protocols. You can configure each serial port to a specific Modbus serial
environment, set up an SID map. After configuration, only the gateway will be visible to Modbus
TCP masters, and all serial devices will be integrated behind it.
Serial Master with Serial Slaves over Internet
Let Modbus serial devices communicate over the Internet
Many Modbus devices communicate over RS-485, which limits the number of devices in a
network to 32 and the transmission distance to 1.2 km.
With the MGate MB3000 Modbus gateway, you can link all Modbus devices over an Ethernet
network. Up to 32 Modbus gateways can be installed in a single control network, so each device
can now be accessed from anywhere the TCP/IP network can reach.
MB3000
MB3000 MB3000 MB3000
RS-485
RS-485
RS-232
RS-232
Modbus/RTU
Master device
Modbus/RTU
Slave devices
Ethernet
Flow meter
Drives
Loop controller
Power measurement
PLC
DCS