Specifications

9-62
Remote I/O Servers
Remote I/O Servers
www.m o x a . c o m e - m a i l : i n f o @ m o x a . c o m
9
0 1
2 3
4 5
6 7
24V 0V
CG CG
0V 0V
24V 24V
0 1
2 3
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
Field Power Input (0 VDC)
Field Power Input (24 VDC)
System Power Input (24 VDC)
System Power Input (0 VDC)
Non-isolation
Switching
Power
Shield Ground
M-7001
0 1
2 3
4 5
6 7
CG CG
N N
P P
0 1
2 3
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (N)
Field Power (P)
Shield Ground
Field Power Input (N)
Field Power Input (P)
*Field Power contact disconnected
*Field Power ranging from
24/48 VDC to 110/220 VAC
M-7002
M-7001 System power expansion, 1.0A / 5 VDC
Input Specifications
System Input Voltage Range: 11 to 28.8 VDC
System Power Input Voltage: Nominal 24 VDC
Field Power Input Voltage: Nominal 24 VDC (+/-20%)
Output Specifications
System Bus Output Voltage: Max. 5 VDC
Field Power Contacts Current: Max. 10A
Wiring: I/O cable max. AWG14
System Modules
System Power Module
The system power expansion module is designed to provide extra power for
connected I/O expansion modules.
If the power requirements of all installed I/O expansion module exceeds 1.5
Amp/5 VDC, you will need to use an M-7001 module.
M-7002 Field power distributor
Input Specifications
Field Power Voltage: 5 VDC, 24 VDC, 48 VDC, 110 VAC, 220 VAC
Output Specifications
Field Power Contacts Current: Max. 10A
Wiring: I/O cable max. AWG14
The field power distributor is designed to isolate different field voltages. For
example, before you connect a 48 VDC or 110 VAC DI/O module to a 24 VDC
DI/O module, you will need an M-7002 field power distributor.