Specifications
Total Solutions for Industrial Device Networking
9-33
Remote I/O Servers
www.m o x a . c o m e - m a i l : i n f o @ m o x a . c o m
9
R2000 Serial
Remote I/O Servers
The ioLogik R2000 series was designed for system integrators to acquire and control remote digital and analog devices over RS-485. Types of digital
on/off devices include proximity switches, mechanical switches, push buttons, optical sensors, LEDs, and light switches. Types of analog devices
include pH, conductivity, temperature, humidity, pressure, flow, actuator, and valves.
The ioLogik R2000 series of servers can work with the standard Modbus protocol. SCADA software or the MXIO DLL library may be used to access
the server.
Linking Input and Output Signals over RS-485
RS-485 is most common wiring standard in many industries. MOXA now offers a high quality line of remote I/O servers that support RS-485 and
provide upgraded functions.
Multi-functional digital I/O with DI/Event Counter and DO/Pulse Output modes
Multi-function analog I/O with mA/mV/Voltage modes
Over-current and over-voltage protection
PLC-grade I/O design that ensures accuracy and reliability during field operation
Remote management of firmware upgrades over RS-485 network
Full Range of DI/O and AI/O Models
Each input signal can be independently configured, with DI/Event Counter modes available for digital inputs and voltage/current modes available for
analog inputs. Each digital output can be independently configured for DO or Pulse Output mode. The analog input channels support various signals
ranging from +/-150 mV to +/-10V at 16-bit resolution. The analog output channels support 0 to 10V and 4 to 20 mA @ 12-bit resolution.
Independent Configuration of Multi-Functional DI/DO and AI/AO Channels
Traditionally, it was difficult for users to update
firmware over RS-485. MOXA now provides
an easy method for updating firmware over
an RS-485 network. This allows users to
perform remote firmware updates, reducing
maintenance time and cost.
Easy Management of Firmware Over RS-485
Traditionally, a PC was required in order to configure a remote I/O server. MOXA offers the optional snap-on LCD
module as an easier way to configure and monitor ioLogik E2000 and R2000 servers.
The LCD module is hot-pluggable, so it may be installed or removed without turning the server off.
Snap-On LCD Module