Specifications
9-32
Remote I/O Servers
Remote I/O Servers
www.m o x a . c o m e - m a i l : i n f o @ m o x a . c o m
9
Digital Output
(2) Digital Output
GND
DO
0
DO
1
DO
2
DO
3
DO
4
DO
5
DO
6
DO
7
DO PWR
-
+
Pin15 Pin 24
DI
5
DI
4
DI
3
DI
8
DI
7
DI
6
DI
11
DI
10
DI
9
DI
2
DI
1
DI
0
DI COM
GND
+
-
Prondmly
Sencor
Shielded
wire
Brown
12 to 24 VDC
NPN open
collector output
DV
Black
Blue
Pin Assignment
Wiring Example
I/O (left to right)
Power and RS-485
(Power Input)
1 2 3
V+ (12-48 V) V- FG
Alarm Port
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DI COM1
DI 0
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
Alarm
DO Power
GND
DO 0
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
GND
(4) Alarm Output
Digital Input (Dry Contact)
Digital Input (Wet Contact)
(1) Dry Contact
(3) Wet Contact
DI
5
DI
4
DI
3
DI
2
DI
1
DI
0
DI COM
GND
DI
2
DI
1
DI
0
DI COM
+
-
Specifications
On-status Voltage: 24 VDC (typical)
Output Current Rating: Max. 200 mA per channel
Optical Isolation: 2 kVrms/3K VDC
Protection:
Over Voltage Protection: +50 VDC
Over Current Limit: 600 mA (typical)
Over Temperature Shutdown: 160°C (min.)
Alarm Port Output
Output: 1, sink type
On-status Voltage: 24 VDC (typical)
Output Current Rating: Max. 200 mA per channel
Optical Isolation: 2 KVrms/3K VDC
Agency Approvals
EMI: FCC part 15, CISPR (EN55022) Class A
EMS: IEC 61000-4-2 (ESD), Level 2/3
IEC 61000-4-3 (RS), Level 2
IEC 61000-4-4 (EFT), Level 2
IEC 61000-4-5 (Surge), Level 3
IEC 61000-4-6 (CS), Level 2
IEC 61000-4-8 (PM), Level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2
IEC 61000-6-4 (EMC)
Safety: UL 508
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Warranty: 2 years
ioMirror E3210: Peer-to-peer I/O server with 8 digital inputs and 8
digital outputs
LDP1602: LCD module with 16 x 2 text and 5 button
Ordering Information