Specifications
Total Solutions for Industrial Device Networking
9-25
Remote I/O Servers
www.m o x a . c o m e - m a i l : i n f o @ m o x a . c o m
9
Pin Signals
1 Tx+
2 Tx-
3 Rx+
6 Rx-
1
8
Pin
1 2 3 4 5 6
Signal
V+ V- FG D+ D- SG
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DI COM
DI0
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI. GND
DO.PWR
DO0
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO.GND
Pin Assignment
Ethernet Power and RS-485
ioLogik E2210: Active Ethernet I/O server with 12 digital inputs and
8 digital outputs
LDP1602: LCD module with 16 x 2 text and 5 button
Ordering Information
I/O (left to right)
Specifications
I/O Mode: DI or Event Counter (up to 900 Hz)
Dry Contact: Logic 0: short to GND, Logic 1: open
Wet Contact: Logic 0: 0 to 3 VDC,
Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type: 12 points / 1 COM
Isolation: 3K VDC
Digital Output
Outputs: 8, sink type
I/O Mode: DO or Pulse Output (up to 1 KHz)
On-state Voltage: 24 VDC nominal
Output Current Rating: Max. 200 mA per channel
Optical Isolation: 3K VDC
Protection: Over temperature shutdown: Min. 170°C
Over current limit: typ. 750 mA/channel
Agency Approvals
EMI: FCC Part 15, CISPR (EN55022) Class A
EMS: IEC61000-4-2 (ESD), Level 2/3
IEC61000-4-3 (RS), Level 2
IEC61000-4-4 (EFT), Level 2
IEC61000-4-5 (Surge), Level 3
IEC61000-4-6 (CS), Level 2
IEC61000-4-8 (PM), Level 1
IEC61000-4-11 (Dip)
EN61000-6-2
EN61000-6-4(EMC)
Safety: UL 508
Shock: IEC60068-2-27
Freefall: IEC60068-2-32
Vibration: IEC60068-2-6
Warranty: 2 years
Wiring Example
Digital Output
(2) Digital Output
Digital Input (Dry Contact)
Digital Input (Wet Contact)
(1) Dry Contact
GND
DO
0
DO
1
DO
2
DO
3
DO
4
DO
5
DO
6
DO
7
DO PWR
-
+
Pin15 Pin 24
DI
5
DI
4
DI
3
DI
8
DI
7
DI
6
DI
11
DI
10
DI
9
DI
2
DI
1
DI
0
DI COM
GND
DI
5
DI
4
DI
3
DI
8
DI
7
DI
6
DI
11
DI
10
DI
9
DI
2
DI
1
DI
0
DI COM
GND
+
-
Prondmly
Sencor
Shielded
wire
Brown
12 to 24 VDC
NPN open
collector output
DV
Black
Blue
(4) Wet Contact