Total Solutions for Industrial Device Networking Remote I/O Servers Remote I/O Servers Introduction Remote I/O Severs Selection Guide 9-2 9-5 Success Stories 9-8 Active Ethernet I/O Introduction ioLogik E2212 Active Ethernet I/O Server with 8 DI, 8 DO, 4 DIO ioLogik E2210 Active Ethernet I/O Server with 12 DI, 8 DO ioLogik E2240 Active Ethernet I/O Server with 8 AI, 2 AO 9-16 9-22 9-24 9-26 Ethernet Peer-to-Peer I/O Introduction ioMirror E3210 Peer-to-Peer I/O Server with 8 DI, 8 DO 9-28 9-31 Seria
Remote I/O Servers User-Friendly Industrial-Quality I/O Simplifies Industrial IT Integration 9 Remote I/O Servers Flexible Remote I/O Solutions for PC-Based Data Acquisition and Control Applications As Ethernet achieves mainstream usage in PC-based data acquisition and control systems, an I/O solution is needed that unleashes the power of Ethernet and Internet technology. MOXA offers a complete range of remote I/O solutions.
Total Solutions for Industrial Device Networking Industrial-Quality Remote I/O Unlike project-based and commercial-grade I/O products, ioLogik remote I/O solutions are equipped with PLC-quality hardware logic control and with the best features of Ethernet and TCP/IP. Multi-functional I/O All I/O channels in the ioLogik 2000 line of remote I/O servers are multi-functional to better handle field applications.
Remote I/O Servers Support for SCADA/OPC-Compliant Modbus Protocol ioLogik remote I/O servers support the most popular standards – Modbus/TCP and Modbus/RTU. Most standard Modbus drivers for SCADA software and OPC Server are compatible with ioLogik servers. Currently, Citect, Wonderware Intouch, iFix, and Kepware OPC Server have been tested. For more information, please refer to www.moxa.com.
Total Solutions for Industrial Device Networking Remote I/O Servers Selection Guide ioLogik E2000 Series Active Ethernet I/O Servers Digital Input/Output Analog Input/Output 9 E2212 E2210 8 12 DI or Event Counter (Event Counter up to 900Hz, configurable filtering time) DI or Event Counter (Event Counter up to 900Hz, configurable filtering time) Dry Contact Yes Yes Wet Contact Source type, 24 VDC PNP/NPN sensor selectable Source Type, 24 VDC Isolation 3K VDC Channels 8 Modes DO or Pulse O
Remote I/O Servers ioLogik R2000 RS-485 Remote I/O Servers Analog Input/Output Digital Input/Output Model R2110 Channels 9 DI or Event Counter (Event Counter up to 50 Hz, configurable filtering time) Modes Input Dry Contact Yes Wet Contact Source Type, 24 VDC Channels Resolution Modes Input Sampling Rate (All Channels) Remote I/O Servers Isolation 3K VDC Isolation Channels 8 Channels DO or Pulse Output (Pulse Output up to 50 Hz, hi/lo width configurable) Modes Output Current Comm.
Total Solutions for Industrial Device Networking ioLogik 4000 Expandable Remote I/O Servers Network Adapters Module Specs NA-4010 NA-4020 Interface Ethernet RS-485 RS-232 Protocols Modbus/TCP, HTTP, Bootp Modbus/RTU, Modbus/ASCII Modbus/RTU, Modbus/ASCII Safety NA-4021 UL 508 Watchdog Yes Digital Inputs Module M-1400 M-1401 M-1410 M-1411 M-1800 M-1801 M-1600 M-1601 M-1450 M-1451 4 4 4 4 8 8 16 16 4 4 Sink Source Sink Source Sink Source Sink Source – Channels Si
Remote I/O Servers Facility Management Airport Security System with Active Ethernet I/O 9 Airport security systems have faced many new challenges over the past few years. The threat of terrorism has caused many countries to introduce major security changes and upgrades to their airports. It is vital for travelers to feel safe and comfortable when using air transportation. Today’s airport administration systems must be effective, modern, and safe.
Total Solutions for Industrial Device Networking Intelligent Transport System More Efficient Automated Parking Using Active Ethernet I/O The often tiresome search for a parking spot is a familiar dilemma for any resident or visitor of a modern city. Automated parking garages help improve the situation by letting drivers know the exact number of available spaces in realtime. However, after a driver enters the lot, a laborious and frustrating search may still be required to find one of those spaces.
Remote I/O Servers Building Automation Using Existing Ethernet to Transmit I/O Signals 9 Many fields already have significant Ethernet penetration, so most information can be made accessible over Ethernet without requiring further wiring. Furthermore, modern buildings are constructed with Ethernet built-in, so Ethernet access is available anywhere in the building. Many smart buildings now rely on Ethernet to transmit environmental data to a control center.
Total Solutions for Industrial Device Networking POS / Retail Automation New Concept for CRM System A decisive factor for success in retail is the ability to develop and retain customer loyalty. A new in-store interactive system has been developed by one European supermarket company to fuel customer interest with games and rewards. The interactive system requires access to real-time visitor tracking data and relies on a specially developed Visual Basic application for control and management.
Remote I/O Servers Warehouse Management Truck Loading Station with Local Control 9 Remote I/O Servers The basic support structure for commercial transport is provided by trucks and truck loading stations. With rising fuel costs and constant pressure to deliver greater quantities in a shorter amount of time, it is essential to maximize operational efficiency wherever possible.
Total Solutions for Industrial Device Networking Unmanned Site Management New Vision for Roadside Cabinet Monitoring with Active Ethernet I/O Many different industries rely on roadside cabinets to provide service to multiple households in a specific area. Different types of equipment may be installed in such cabinets, such as traffic devices or telecom servers. Roadside cabinets were primarily used to serve rural and remote areas, but are now common in urban areas as well.
Remote I/O Servers Machine Room Management Active Ethernet I/O for SNMP-based Remote Site Monitoring 9 Centralized server room management is mainly achieved using SNMP-based solutions, in fields such as the telecom industry, the military, universities, and many others. However, SCADA systems are the typical choice for monitoring environmental information such as device open/close status, temperature levels, and enclosure humidity levels.
Total Solutions for Industrial Device Networking Machine Builder Ethernet I/O Server Designed for Easy Implementation Developing countries rely heavily on the building construction industry, and the availability of concrete can be a critical factor in a nation’s development. To achieve more efficient concrete production, companies have increasingly relied on automated systems. An excellent solution involves using MOXA’s I/O servers as part of a smart concrete production plant.
Remote I/O Servers ioLogik E2000 Active Ethernet I/O New Generation I/O that Talks over Ethernet 9 Remote I/O Servers Active Ethernet I/O is a new concept for PC-based data acquisition and control that introduces proactive, condition-based reporting and control of I/O devices. Unlike traditional I/O servers, which are passive and must be polled for data, Active Ethernet I/O servers can automatically report and control I/O status based on user-specified conditions.
Total Solutions for Industrial Device Networking Why choose Active Ethernet I/O? Click&Go for reduced configuration time TFTP Support • Local logic control with no learning curve, no third-party programming, and no maintenance fees Store and Copy settings for mass deployment using TFTP or Windows utility The Active Ethernet I/O server’s configuration, including IP address, I/O configuration, and Click&Go logic can be exported to a file using TFTP or the ioAdmin Windows utility.
Remote I/O Servers Active Ethernet I/O: Proactive event notification, reduced time and cost Implementation of Active Ethernet I/O is flexible and easy. Active Ethernet I/O servers support multiple protocols for data transmission, including TCP/UDP, SNMP trap, SMTP (e-mail), and Modbus/TCP. Administrators can set up condition-based reporting and control in just minutes using the patent-pending, intuitive Click&Go logic interface, which requires no programming knowledge.
Total Solutions for Industrial Device Networking Click&Go: Four steps to smarter I/O control Click&Go logic control is the key to turning an ioLogik E2000 server into an intelligent Active Ethernet I/O server. Its intuitive, instantly understandable interface provides sophisticated alarm control and messaging. With Click&Go, you have complete control over what, when, and where to transmit.
Remote I/O Servers Step 3: Download logic to server Download logic Stepdefined, 3 one click in When the I/O control logic has been completely ioAdmin downloads the entire set of rules onto your ioLogik E2000 Ethernet I/O server. The server will automatically restart with the ruleset loaded. Note that the ruleset still needs to be activated for Active Ethernet I/O operation to begin.
ntelliegence gramming What's Up Software What's Up Software HP Openview/What's Up Software Supports SNMP read/write/trap Supports I/O control using SNMP management software ActivePeer-to-Peer Ethernet I/O canI/O be used for automatic without Controller notification of I/O events by e-mail. Messages areWatertank completely customizable and can include dynamic fieldsHighsuch as I/O status or current Low time.
Remote I/O Servers E2212 Active Ethernet I/O Server with 8 DI, 8 DO, and 4 DIO Features Selectable digital I/O combination by software Accepts PNP or NPN sensors Instant event reporting by TCP/UDP/e-mail/SNMP trap Easy local control without programming by patented Click&Go logic 9 Windows VB and Windows/WinCE/Linux C API Peer-to-Peer I/O without controller Remote I/O Servers Introduction Flexible digital input/output configuration within one Ethernet DIO The ioLogik E2212 provides system integrators wi
Total Solutions for Industrial Device Networking Specifications Agency Approvals Low Speed Counter/Frequency: 900 Hz, power off storage Over Voltage Protection: +36 VDC Counter Memory: 48 Bytes EMI: FCC part 15, CISPR (EN55022) Class A EMS: IEC 61000-4-2 (ESD), Level 2/3 IEC 61000-4-3 (RS), Level 2 IEC 61000-4-4 (EFT), Level 2 IEC 61000-4-5 (Surge), Level 3 IEC 61000-4-6 (CS), Level 2 IEC 61000-4-8 (PM), Level 1 IEC 61000-4-11 (DIP) IEC 61000-6-2 IEC 61000-6-4 (EMC) Safety: UL 508 Shock: IEC 60068-2-27 F
Remote I/O Servers E2210 Active Ethernet I/O Server with 12 Digital Inputs, 8 Digital Outputs Features Actively transfer I/O data in real-time over Ethernet Easy-to-use Click&Go™ Logic for local output control and messaging 12-point 24 VDC digital input with DI/Event counter 9 8-point 24 VDC digital output as pulse output 10/100 Mbps Ethernet with Modbus/TCP protocol connecting up to 10 hosts SNMP to I/O mapping that works with Network Management System Remote I/O Servers Quick programming library for
Total Solutions for Industrial Device Networking Specifications I/O Mode: DI or Event Counter (up to 900 Hz) Agency Approvals Dry Contact: Logic 0: short to GND, Logic 1: open EMI: FCC Part 15, CISPR (EN55022) Class A Wet Contact: Logic 0: 0 to 3 VDC, Logic 1: 10 to 30 VDC (DI COM to DI) EMS: IEC61000-4-2 (ESD), Level 2/3 IEC61000-4-3 (RS), Level 2 IEC61000-4-4 (EFT), Level 2 IEC61000-4-5 (Surge), Level 3 IEC61000-4-6 (CS), Level 2 IEC61000-4-8 (PM), Level 1 IEC61000-4-11 (Dip) EN61000-6-2 EN61000-6-4
Remote I/O Servers E2240 Active Ethernet I/O Server with 8 Analog Inputs, 2 Analog Outputs Features Actively transfer I/O data in real-time over Ethernet Easy-to-use Click&Go™ Logic for local output control and messaging 8-channel analog input for mV, voltage, current signal with wireoff detection (at 4-20mA) 9 2-channel analog output for voltage, current actuator control Connects up to 10 hosts SNMP to I/O mapping that works with Network Management System Remote I/O Servers Quick programming library f
Total Solutions for Industrial Device Networking Specifications Freefall: IEC60068-2-32 Analog Output Vibration: IEC60068-2-6 Outputs: 2 Analog Input Resolution: 12-bit Input: 8 Output Range: 0 to 10V, 4 to 20 mA Resolution: 16-bit Drive Voltage: 15 VDC for current output Input Range: +/-150 mV, +/-500 mV, +/-5 V, +/-10 V, 0 to 20 mA, 4 to 20 mA Data Format: 16-bit integer (2’s complement) Data Format: 16-bit integer (2’s complement) CMR @ 50/60 Hz: 95 dB min. Accuracy: +/- 0.
Remote I/O Servers E3000 Peer-to-Peer I/O Servers Direct input-to-output communication over an IP network 9 Remote I/O Servers The ioMirror E3000 Ethernet I/O server is designed as a cable replacement solution that sends input signals to remote outputs over an Ethernet or IP network. ioMirror servers can be used to connect remote sensor signals to PLC controllers, DCS systems, or display devices over a network, without installing additional signal wires.
Total Solutions for Industrial Device Networking No PLC or PC controllers, and no programming Unlike traditional solutions, a PLC or PC is not required as a controller to transmit input signals over a network. The ioMirror hardware handles all signal mapping automatically, with no ladder or C programming required. With ioMirror, input signals can be easily extended over Ethernet from one server to another, without programming or a separate controller.
Remote I/O Servers ioMirror servers in different network infrastructures #1 Ethernet network #2 Fiber Ethernet network Exiting Etnernet Without Controller Output Module Redundant Ring Input Module Output Module Input Module 9 Up to 12 Inputs Up to 8 Outputs #3 Wireless LAN network Remote I/O Servers Input Module Output Module Lower wiring costs for industrial or business automation ioMirror is the easiest and fastest way to connect input signals to remote outputs over Ethernet and IP networks.
Total Solutions for Industrial Device Networking E3210 Ethernet Peer-to-Peer I/O Server 8 Digital Inputs, 8 Digital Outputs Features Remote digital input mapped to local digital output over Ethernet High speed peer-to-peer I/O Copy sensor signals to up to sixteen locations Quick and easy utility and web-based settings Local alarm and remote alarm message Support Modbus/TCP for remote monitoring 9 Remote I/O Servers Introduction Direct input-to-output communication over IP Split sensor signals to sixteen
Remote I/O Servers Specifications On-status Voltage: 24 VDC (typical) Agency Approvals Output Current Rating: Max.
Total Solutions for Industrial Device Networking R2000 Serial Remote I/O Servers Linking Input and Output Signals over RS-485 The ioLogik R2000 series was designed for system integrators to acquire and control remote digital and analog devices over RS-485. Types of digital on/off devices include proximity switches, mechanical switches, push buttons, optical sensors, LEDs, and light switches. Types of analog devices include pH, conductivity, temperature, humidity, pressure, flow, actuator, and valves.
Remote I/O Servers R2110 RS-485 Remote I/O Server with 12 Digital Inputs, 8 Digital Outputs Features 12-point 24 VDC digital input with DI/Event Counter mode, software selectable filtering time 8-point 24 VDC digital output with Pulse Output mode, software selectable pulse width LED indicators for all I/O channels 9 Over temperature protection (up to 170°C) Over-current protection (750 mA/channel) Easy-to-use, quick programming lib for VB, VC++, BCB Remote I/O Servers Easy firmware upgrade over RS-485
Total Solutions for Industrial Device Networking Pin Assignment Power and RS-485 Pin Signal 1 V+ 2 V- 3 FG 4 D+ 5 D- 6 SG 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DI COM DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI. GND DO.PWR DO0 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO.
Remote I/O Servers R2140 RS-485 Remote I/O Server with 8 Analog Inputs, 2 Analog Outputs Features 8-channel analog input for mV, voltage, current signal with wire-off detection (at 4 to 20 mA) 2-channel analog output for voltage, current actuator control 16-bit resolution analog input, 12-bit resolution analog output 9 Easy-to-use, quick programming lib for VB, VC++, BCB NIST-Traceability calibration for analog I/O channels Easy firmware upgrade over RS-485 Remote I/O Servers Specifications Serial Inte
Total Solutions for Industrial Device Networking Pin Assignment Power and RS-485 Pin 1 2 3 4 5 6 Signal V+ V- FG D+ D- SG 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Vin0+ Vin0- Vin1+ Vin1- Vin2+ Vin2- Vin3+ Vin3- Vin4+ Vin4- Vin5+ Vin5- Vin6+ Vin6- Vin7+ Vin7- Vout0+ Vout0- Iout0+ Iout0- Vout1+ Vout1- Iout1+ Iout1- I/O (left to right) Wiring Example Analog Output 1 + 1 - lout 1 - 1 + lout 0 Vout 0 + Vout 0 - (1)
Remote I/O Servers LDP1602 LCD Module LDP1602 LCD Module for ioLogik 2000 Series Features Hot-pluggable display module for ioLogik Active Ethernet I/O and serial remote I/O servers Easy, portable configuration kit for IP display and configuration Direct display for analog value and digital input, counter status 9 No battery required (powered by I/O server) Supports ioLogik E2000 series, ioLogik R2000 series and ioMirror E3000 series Remote I/O Servers Installing the LCD Module 1.
Total Solutions for Industrial Device Networking 4000 Series Expandable Remote I/O Servers Expandable Remote I/O Solutions for Data Acquisition and Control Features Remotely acquire sensor data and control I/O points via Ethernet, RS-485, and RS-232 Full range of digital and analog I/O modules Expandable up to 32 modules for a maximum of 512 DI/O points or 124 analog channels 9 Modular package for fast swap and maintenance DLL library for easy programming Remote I/O Servers Standard Modbus/TCP/RTU/ASC
Remote I/O Servers Expandable I/O Modules for a Full Range of I/O Combinations Modbus/TCP Fast Ethernet Modbus/RTU RS-485/232 Network Adapter 9 I/O Expansion Modules Types of Network Adapter Ethernet RS-485 RS-232 I/O Module Remote I/O Servers Digital Input Digital Output Analog Input Analog Output Type Channels Type Channels Type Channels Types Channels 24 VDC 4, 8, 16 24 VDC 4, 8, 16 0 to 20 mA 4 0 to 20 mA 2 48 VDC 4 24 VDC w/ Diag 4 4 to 20 mA 4 4 to 20 mA 2 110 VA
Total Solutions for Industrial Device Networking Automatic Search for Installed ioLogik Servers ioAdmin can automatically search for installed ioLogik servers. The automatic search function supports both Ethernet and RS-232/485 searching. 9 Remote I/O Servers Online Documentation Traditionally, engineers needed to manually prepare a wiring handbook. ioAdmin provides convenient online documentation that engineers may use when planning or troubleshooting field wiring.
Remote I/O Servers Remote Configuration ioAdmin is a powerful, Windows-based configuration and management tool. You may use ioAdmin to modify the IP address, update communication parameters, and configure all other settings easily. In addition, ioAdmin can be used to configure ioLogik I/O servers from a remote host. This means that ioLogik servers may be configured from anywhere over the Ethernet, which may help reduce operating costs.
Total Solutions for Industrial Device Networking Check Remote I/O Status with a Web Browser ioAdmin is the main configuration interface for ioLogik servers. However, you can also check some information using the ioLogik server’s web console.
Remote I/O Servers Network Adapter Modules NA-4010 Ethernet Network Adapter ioLogik 4000 System Power (5 VDC) System Power (GND) Modbus TCP/IP NA-4010 SYS LINK ACTIVE I/O Field Power System Bus Non-isolation Switching Power 9 Remote I/O Servers 00 11 0V CH0 24V CH0 System Power (0 VDC) 22 33 SG CH0 SG CH0 Shielding Ground 4 5 CH0 0V CH0 0V Field Power (0 VDC) 66 77 24V CH0 24V CH0 System Power (24 VDC) Field Power (24 VDC) Field Power (0 VDC) Field Power (24 VDC) Specifications Network Prot
Total Solutions for Industrial Device Networking Network Adapter Modules NA-4020 RS-485 Network Adapter NA-4021 RS-232 Network Adapter ioLogik 4000 System Power (5 VDC) System Power (GND) Modbus RS-485 NA-4020 SYS TxD RxD Field Power I/O System Bus Non-isolation Switching Power System Power (0 VDC) 22 33 SG SG Shielding Ground 4 5 0V 0V CH0 Field Power (0 VDC) 66 77 24V CH0 24V CH0 System Power (24 VDC) Field Power (24 VDC) Field Power (0 VDC) Field Power (24 VDC) 9 Remote I/O Servers 00 11 2
Remote I/O Servers Digital Input Modules 4/8-channel 24/48 VDC Digital Input Modules M-1400 Status 9 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 0 1 CH0 CH1 Remote I/O Servers 2 3 CH2 CH3 6 7 24V 24V Field Power (0 VDC) Field Power (24 VDC) Status 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 0 1 CH0 CH1 2 3 CH2 CH3 6 7 24V 24V Field Power (0 VDC) Field Power (24 VDC) Status 0 4 1 5 System Power (5 VDC) System Power (GND) System Bus Power Consumption: Max.
Total Solutions for Industrial Device Networking Digital Input Modules 4/8-channel 24/48 VDC Digital Input Modules M-1801 Status 0 4 1 5 System Power (5 VDC) System Power (GND) System Bus 0 1 CH0 CH1 4 5 CH4 CH5 General Specifications 6 7 CH6 CH7 Field Power (0 VDC) Field Power (24 VDC) Field Power (24 VDC) Field Power (0 VDC) 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 0 1 CH0 CH1 2 3 CH2 CH3 Power Consumption: Max.
Remote I/O Servers Digital Input Modules 16-channel 24 VDC Digital Input Modules M-1600 Status 9 0 4 8 12 1 5 9 13 System Power (5 VDC) System Power (GND) System Bus 2 61014 3 71115 Remote I/O Servers 0 1 Ch0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0V 0V M-1601 Status 0 4 8 12 1 5 9 13 Field Power (0 VDC) Field Power (24 VDC) System Power (5 VDC) System Power (GND) System Bus 2 61014 3 71115 0 1 Ch0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0V 0V 9-48 Inputs per Mod
Total Solutions for Industrial Device Networking Digital Input Modules 4-channel 110V/240 VAC Digital Input Modules M-1450 Status 0 System Power (5 VDC) System Power (GND) System Bus 1 M-1450 4 digital inputs, 110 VAC Input Specifications 3 0 1 CH0 CH1 2 3 CH2 CH3 General Specifications 4 5 N N 6 7 L L Field Power (110 VAC N) Field Power (110 VAC L) Power Consumption: Max.
Remote I/O Servers Digital Output Modules 4/8-channel 24 VDC Digital Output Modules M-2400 4 digital outputs, sink, 24 VDC, 0.5A Output Specifications 9 M-2400 Status 0 System Power (5 VDC) System Power (GND) System Bus 1 2 Remote I/O Servers 3 0 1 CH0 CH1 L 2 3 CH2 CH3 L 4 5 24V 24V 6 7 24V 24V Field Power (0 VDC) Field Power (24 VDC) Outputs per Module: 4 points, sink type On-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.
Total Solutions for Industrial Device Networking Digital Output Modules 4/8-channel 24 VDC Digital Output Modules M-2800 8 digital outputs, sink, 24 VDC, 0.5A Output Specifications M-2800 Status 0 4 1 5 System Power (5 VDC) System Power (GND) System Bus 2 6 3 7 L 2 3 CH2 CH3 L 4 5 CH4 CH5 L 6 7 CH6 CH7 L Field Power (0 VDC) Field Power (24 VDC) Field Power (24 VDC) Field Power (0 VDC) General Specifications Power Consumption: Max.
Remote I/O Servers Digital Output Modules 4-channel Digital Output Modules with Self-Diagnostics M-2402 4 digital outputs, self-diagnostics, sink, 24 VDC, 0.5A 9 M-2402 Status 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 Remote I/O Servers 0 1 CH0 CH1 L 2 3 CH2 CH3 L 4 5 24V 24V 6 7 24V 24V Field Power (0 VDC) Field Power (24 VDC) Output Specifications Outputs per Module: 4 points, sink type On-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.
Total Solutions for Industrial Device Networking Digital Output Modules 4-channel Digital Output Modules with Self-Diagnostics M-2404 4 digital outputs, self-diagnostics, sink, 24 VDC, 2A Output Specifications M-2404 Status 0 System Power (5 VDC) System Power (GND) System Bus 1 0 1 CH0 CH1 L 2 3 CH2 CH3 L 4 5 24V 24V 6 7 24V 24V Field Power (0 VDC) Field Power (24 VDC) 9 Remote I/O Servers 2 3 Outputs per Module: 4 points, sink type On-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.
Remote I/O Servers 16-channel Digital Output Modules M-2600 16 digital outputs, sink, 24 VDC, 0.3A 9 M-2600 Status 0 4 8 12 1 5 9 13 Output Specifications System Power (5 VDC) System Power (GND) System Bus 2 61014 3 71115 Remote I/O Servers 0 1 Ch0 1 L 2 3 L 4 5 L 6 7 L 8 9 L 10 11 L 12 13 L 14 15 L 0V 0V General Specifications 24V 24V 18 19 Outputs per Module: 16 points, sink type On-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.
Total Solutions for Industrial Device Networking Digital Output Modules 2-channel Relay Output Module M-2250 2 digital outputs, relay, 24 VDC/230 VAC, 2A Output Specifications M-2250 Status 0 System Power (5 VDC) System Power (GND) System Bus 1 L 2 3 Ch0 Ch1 4 5 L1 L1 COM (to N or 0 VDC) 6 7 L2 L2 Field Power (N or 0 VDC) Field Power (230 VAC or 24 VDC) * Field Power distributor required when the field power is not 24 VDC.
Remote I/O Servers Analog Input Modules General Resolution M-3400 4 analog inputs, 0 to 20 mA, 12-bit M-3402 4 analog inputs, 4 to 20 mA, 12-bit 9 M-34xx Status 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 Remote I/O Servers Current 0 to 20mA (M-3400/3401) Current 4 to 20mA (M-3402/3403) 0 1 CH0 CH1 2 3 CH2 CH3 Resolution in Ranges: 12 bits, 4.88 µA/bit (M-3400) 12 bits, 3.
Total Solutions for Industrial Device Networking Analog Input Modules High Resolution M-3401 4 analog inputs, 0 to 20 mA, 14-bit M-3403 4 analog inputs, 4 to 20 mA, 14-bit M-34xx Status 0 System Power (5 VDC) System Power (GND) System Bus 1 2 3 CH0 CH1 2 3 CH2 CH3 General Specifications 4 5 G G 6 7 CG CG Resolution in Ranges: 14 bits, 1.22 µA/bit (M-3401) 14 bits, 0.
Remote I/O Servers Analog Input Modules Temperature Sensing M-6200 2 analog inputs, RTD: PT100, JPT100 Input Specifications M-6200 9 Status 0 System Bus 1 Remote I/O Servers Sensor Types: PT50, PT100, PT200, PT500, PT1000, JPT100, JPT200, JPT500, JPT1000, NI100, NI200, NI500, NI1000, NI120, CU10, Resistance 100 mohm/bit, Resistance 10 mohm/bit, Resistance 20 mohm/bit Data Format: 16-bit integer (2’s complement) Resolution: 0.1°C / 10 mohm Accuracy: +/- 0.1%, FSR @ 25°C +/- 0.
Total Solutions for Industrial Device Networking Analog Input Modules Temperature Sensing M-6201 2 analog inputs, thermocouple M-6201 System Power (5 VDC) System Power (GND) Status 0 Input Specifications 1 Voltage 0 to 10V 0 1 CH0 CH1 Thermocouple CH1- 4 5 G G 6 7 CG CG Remote I/O Servers 2 3 CH0 CH1 CH1+ 9 Sensor Types: Type J/K/T/E/R/S/B/N/L/U/C/D mV input 10 µV/bit, 2 µV/bit Data Format: 16-bit integer (2’s compliment) Resolution: 0.1°C / 10 mohm Accuracy: +/- 0.1%, FSR @ 25°C +/- 0.
Remote I/O Servers Analog Output Modules General Resolution M-4201 2 analog outputs, 0 to 20 mA, 12-bit M-4202 2 analog outputs, 4 to 20 mA, 12-bit 9 M-420x Status 0 System Power (5 VDC) System Power (GND) System Bus 1 Remote I/O Servers 0 1 CH0 CH1 Current 0 to 20mA (M-4201) Current 4 to 20mA (M-4202) R<500 Ohm 2 3 NC NC Resolution in Ranges: 12 bits, 4.88 µA/bit (M-4201) 12 bits, 3.
Total Solutions for Industrial Device Networking System Modules When to Use a System Module Power expansion module The system power expansion module is designed to provide extra power for connected I/O expansion modules. Each network adapter can provide 1.5 Amp/5 VDC. If you require more power for your installed I/O expansion modules, you will need to use an M-7001 module. However, please note that the M-7001 can only provide 1 Amp per 5 VDC. 9 Remote I/O Servers ...................
Remote I/O Servers System Modules System Power Module M-7001 System power expansion, 1.0A / 5 VDC Input Specifications 9 M-7001 System Power (5 VDC) System Power (GND) Output Specifications System Bus Remote I/O Servers Non-isolation Switching Power 0 1 24V 0V 2 3 CG CG System Input Voltage Range: 11 to 28.8 VDC System Power Input Voltage: Nominal 24 VDC Field Power Input Voltage: Nominal 24 VDC (+/-20%) System Bus Output Voltage: Max. 5 VDC Field Power Contacts Current: Max.
Total Solutions for Industrial Device Networking System Modules System Power Module M-7803 System Power (5 VDC) System Power (GND) System Bus M-7803 Potential distributor, 8-ch, shield signal Input Specifications 9 Field Power Voltage: Shield signal Output Specifications Field Power Contacts Current: Max. 10A Wiring: I/O cable max.
Remote I/O Servers System Modules System Power Module M-7806 System Power (5 VDC) System Power (GND) System Bus 9 M-7806 Potential distributor, 4-ch/24 VDC, 4-ch/0 VDC Input Specifications Field Power Voltage: 24 VDC/0 VDC Output Specifications 0 1 Field Power Contacts Current: Max. 10A Wiring: I/O cable max.
Total Solutions for Industrial Device Networking Ordering Information Model No. Network Adapter Model No.
Remote I/O Servers MXIO DLL Library Quick Programming—Only 5 Steps to Touch the Real World For small-scale data acquisition systems, you may consider developing your own application in-house, rather than using an expensive SCADA package. MOXA provides a powerful MXIO library for different programming languages, including Visual Basic, Visual C++, and Borland C++ Builder, so you can build your application quickly.