Specifications
5-38
www.moxa.com
info@moxa.com
Remote Monitoring Solutions
Industrial I/O >
Temperature Input Modules
5
Temperature Input Modules
2-channel temperature input modules, RTD or thermocouple input
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
0 1
2 3
4 5
6 7
CH0 CH1
CH0 CH1
G
CG CG
0 1
2 3
G
RTD
Shielding Ground
CH1-A
CH1-B
M-6200
Status
0
1
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
0 1
2 3
4 5
6 7
CH0 CH1
CH0 CH1
G
CG CG
0 1
2 3
G
Voltage 0 to 10V
Shielding Ground
CH1+
CH1-
Thermocouple
M-6201
Status
0
1
Ordering Information
Analog Input Modules
Specs
Model
M-3802 M-3810 M-6200 M-6201
Channels 8822
Current 4 to 20 mA --- --- ---
Voltage – 0 to 10V --- ---
Connector RTB RTB RTB RTB
Resolution 12-bit 12-bit --- ---
Isolation Optical isolation
Sensor
Input
--- ---
RTD
(ohm)
Thermo-couple
(mV)
M-6200: 2 analog inputs, RTD: PT100, JPT100
Sensor Types:
• PT50, PT100, PT200, PT500, PT1000 (resistance 100 milli-ohms/bit)
• JPT100, JPT200, JPT500, JPT1000 (resistance 10 milli-ohms/bit)
• NI100, NI200, NI500, NI1000, NI120, CU10 (resistance 20 milli-ohms/bit)
Resolution: 0.1°C/10 milli-ohms
Data Format: 16-bit integer (2’s complement)
Accuracy:
• ±0.1%, FSR @ 25°C
• ±0.3%, FSR @ 0°C, 60°C
Input Impedance: 500K ohms
Conversion Time: 200 ms for all channels
Diagnostics: Range over (if range over, data=Dx8000)
Power Consumption: Max. 80 mA @ 5 VDC
Isolation: I/O to logic (photocoupler isolation)
Wiring: I/O cable max. AWG14
M-6201: 2 analog inputs, thermocouple
Sensor Types:
Type J/K/T/E/R/S/B/N/L/U/C/D
(mV input 10 µV/bit, 2 µV/bit)
Resolution: 0.1°C/10 µV
Data Format: 16-bit integer (2’s complement)
Accuracy:
• ±0.1%, FSR @ 25°C
• ±0.3%, FSR @ 0°C, 60°C
Input Impedance: 500K ohms
Conversion Time: 200 ms for all channels
Diagnostics: Range over (if range over, data=Dx8000)
Power Consumption: Max. 80 mA @ 5 VDC
Isolation: I/O to logic (photocoupler isolation)
Wiring: I/O cable max. AWG14