Specifications

5-36
www.moxa.com
info@moxa.com
Remote Monitoring Solutions
Industrial I/O >
Digital Output Modules
5
4-channel relay output modules
Ordering Information
Digital Output Modules
Specs
Model
M-2800 M-2801 M-2600 M-2601 M-2450
Channels 8 8 16 16 4
Sink/Source Sink Source Sink Source Relay
Connector RTB RTB 20-pin 20-pin RTB
Voltage 24 VDC 24 VDC 24 VDC 24 VDC
230 VAC/
24 VDC
Current 0.5A 0.5A 0.3A 0.3A 2.0A
Isolation Optical isolation
Diagnostics --- --- --- --- ---
M-2450: 4 relay outputs, 24-VDC/230-VAC, 2 A
Outputs per Module: 2 channels, relay
Relay Type:
• Form A, Normally Open (N.O.)
• Single Pole, Single Throw (SPST)
Output Voltage Range: Load dependent
• 5 to 28.8 VDC @ 2 A resistive
• 48 VDC @ 0.8 A resistive
• 110 VDC @ 0.3 A resistive
• 250 VAC @ 2 A resistive
Output Current Rating: At rated power
• 2 A @ 5 to 28.8 VDC
• 0.8 A @ 48 VDC
• 0.5 A @ 110 VDC
• 2 A @ 250 VAC
Min. Load: 100 µA, 100 m VDC per point
Max. On-state Voltage Drop: 0.5 V @ 2 A, resistive load, 24 VDC
Off-state Leakage Current: Max. 1.5 mA
Common Type: 1 channel for 1 COM
Power Consumption: Max. 65 mA @ 5 VDC
24V24V
0V0V
1514
1312
1110
98
76
54
32
1Ch0
0 1
18 19
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
L
L
L
L
L
L
L
L
M-2601
Status
7
1115
6
10
14
1
5
9
13
0
4
8 12
M-2601: 16 digital outputs, source, 24 VDC, 0.3 A
Outputs per Module: 16 channels, source type
Output Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDC
On-state Voltage Drop: Max. 0.3 VDC @ 25°C
On-state Current: Min. 1 mA per channel
Off Leakage Current: Max. 50 µA
Output Current Rating:
• Max. 0.3 A per channel
• Max. 4 A per common
Common Type: 16 channels for 2 COMs (single common)
Power Consumption: Max. 80 mA @ 5 VDC
M-2450
Status
0
2
3
1
C0
C3
C1
C2