Specifications
Industrial Networking Solutions
5-29
info@moxa.com
www.moxa.com
5
Industrial I/O >
ioLogik R2110
RS-485 remote I/O with 12 digital inputs and 8 digital outputs
ioLogik R2110
Specifi cations
12-channel 24 VDC digital inputs with DI Event Counter mode, and ›
software selectable fi ltering time
8-channel 24 VDC digital outputs with pulse output mode and ›
software selectable pulse width
LED indicators for all I/O channels ›
Over-temperature protection (up to 175°C) ›
Over-current protection (400-mA/channel) ›
Easy-to-use, quick programming library for VB, VC++, BCB, .NET ›
Firmware upgradable over RS-485 ›
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DI.COM
DI0
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI.GND
DO.PWR
DO0
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO.GND
Pin Assignment
I/O (left to right)
Ordering Information
Digital Input
Channels: 12, source type
I/O Mode: DI or Event Counter (up to 50 Hz)
Dry Contact:
Logic 0: short to GND
Logic 1: open
Wet Contact:
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC
(DI COM to DI)
Common Type: 12 points per COM
Isolation: 3K VDC or 2K Vrms
Digital Output
Channels: 8, sink type, 36 VDC, 200 mA
I/O Mode: DO or Pulse Output (up to 50 Hz)
Output Current Rating: Max. 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Output Frequency: 50 Hz
ioLogik R2110: RS-485 remote I/O with 12 digital inputs and 8 digital outputs
LDP1602: LCD module with 16 x 2 text display and 5 buttons
The certifi cation logos shown here apply to some or all of the products in this
section. For details, see “Regulatory Approvals” under “Specifi cations” below.